WARRANTY & SUPPORT
6.

Maintenance

The DPC200 contains no wearing or consumable parts. Servicing is not required.
On request, Arthur Grillo GmbH offers an annual calibration with factory certificate.
For information, please contact:
Arthur Grillo GmbH
7.

Warranty

Warranty and liability claims for personal and property damage are excluded if they are
caused by one or more of the following reasons:
Improper use of the device.
Improper installation, commissioning, operation and maintenance of the device.
Unauthorized modifications to the device beyond the intended use.
Disasters due to external influences and force majeure.
8.

Troubleshooting

Description
Display does not show
anything
Measurement stays zero
Measuring error
Error remains
9.

Disposal

Dispose of parts so as not to endanger human health or the environment. Follow the laws
in the country of use for disposing of electronic components and devices during disposal.
12
Activity
Check electrical connection
Function test with a slight pressure increase in measu-
ring mode for differential pressure
Perform zeroing as described in chapter 4.5.
Contact manufacturer
Doc.-no.: DPC200_04_EBM_US
Phone: +49 21 02 - 47 10 22
Fax:
+49 21 02 - 47 58 82
Issue: 06/2018