Arthur Grillo DPC200-R Manuel d'installation et d'utilisation - Page 15
Parcourez en ligne ou téléchargez le pdf Manuel d'installation et d'utilisation pour {nom_de_la_catégorie} Arthur Grillo DPC200-R. Arthur Grillo DPC200-R 16 pages. Airflow / pressure controller
9.
Disposal
Dispose of parts so as not to endanger the human health or environment. Follow the laws
in the country of use for disposing of electronic components and devices during disposal.
10.
Specifications
Measuring medium:
Measuring principle:
Lowest span:
Highest span:
Overpressure protection:
Static pressure:
Pressure connections:
Enclosure:
Electrical connections:
Supply voltage:
Current consumption:
Output:
Alarm output:
Display:
Mode:
Controlling algorithm:
Setpoints:
Protection class:
Ambient temperature:
Storage temperature:
Weight:
Mounting:
Interference / emission:
Influences / limits:
Air or inert gases
Silicon diaphragm with spring and differential transformer
0...50 Pa
0...6000 Pa
0.2 bar
max. 0.2 bar
tubing 5 mm ø or 6 mm ø
UL 94 HB; Case polyamid, cover ABS
cable inlet M16x1.5, screw terminal
Electronic protection against reversed polarization
20...30 Vdc; 24 Vac (±15%)
approx. 10 mA @ 24 Vdc, and approx 20 mA with relay
0...10 V (I
max
Relay 250 Vac / 10 A
LCD-Display, 2 x16 characters
Measuring mode or controlling mode
PI
2 setpoints adjustable within software,
Setpoints are selectable with floating contact input
IP 54 according EN 60529
-10...50 °C
-25...60 °C
approx. 250 g
vertical, position dependence by turning of 90°: approx. 25 Pa
according EN 61000-6-2, EN 61000-6-3, CE mark
Zero error:
Sum of linearity and hysteresis
(depends on measuring range):
Temperature drift, zero point:
Temperature drift, span:
Doc.-no.: DPC200-R_02_EN
= 0.4 mA @ 10 Vdc, I
Issue: 06/2018
SPECIFICATIONS
= 2 mA @ 20 Vdc)
max
± 0.75 %
± 0.5 % ... ± 1 %
± 0.3 % / 10 K
± 0.2 % / 10 K
15