BTS(Battery Temperature Sensing)
4.4
Environmental
4.4
Environmental
Operation temperature
Relative humidity
Noise
Storage Conditions Temperature
Cooling
Safety
4.5
Mechanical
4.5
Mechanical
Dimension (D x W x H) mm
Unit Weight
Gross Weight
The battery temperature sensor allows the charge controller to
continuously adjust charge voltage / charge current based on
actual battery temperature.
When the battery temperature is over 40 °C, unit will reduce
the charging voltage to Float voltage, also it will reduce the
Max charging current by 10% with every two degrees of
temperature rise.
When the battery temperature is over 50 °C, unit will shut
down.
Nominal ambient temperature: 25℃
Operating Ambient Temperature range: -10℃to 40℃ ( if
the temperature is over 90℃ on the DC-DC heat sink, the
Charger Current will derate to 50%; if the temperature is
over 105℃, the unit will shut down.)
5~95% without condensation
Unit requirements: below 50dB (A) measured at a 3
foot distance with fan pn.
-20°C to +80°C
Smart fan control
Condition
Heat Sink
Temperature
Charger Current
UL458, CSA 22.2#107.1
10.25" * 6.75" * 3.25"
6.5 lb
7 lb
AIMS Power
9550 Gateway Drive
Reno, NV 89511
www.aimscorp.net
775-359-6703
- 11 -
T<50
50
≤T<60
T≥60
I <15%
15%≤ I <25%
I ≥25%
Speed
OFF
50%
100%
OFF
50%
100%