4. Connect devices to be powered:
a. For Power Supply Board connect to the terminals marked [– DC +].
b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked
[1P & 1N through 4P & 4N] (Fig. 3, pg. 4) 1 to 8 marked [1P & 1N through 8P & 8N] (Fig. 4, pg. 4)
or 1 to 16 marked [1P & 1N through 16P & 16N] (Fig. 5, pg. 4), carefully observing correct polarity.
*Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board.
When servicing the unit AC mains should be removed.
5. When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked [– BAT +]
(battery leads included). Note: When batteries are not used, a loss of AC will result in the loss of output voltage.
6. Connect appropriate signaling notification devices to the AC Fail & Low Bat supervisory relay outputs
marked [NC, C, NO] (Fig. 1a, below).
Fig. 1
Wire
Strap
(from
Fig. 1a
Enclosure
to Door)
NC
C NO
NC C
NO
- 2 -
CAUTION: De-energize unit prior to servicing. For continued protection
against fire hazard replace fuse with the same type and rating, 15A, 32V.
Earth
Ground
115 power
Power Supply
mains
Board
AC FAIL
LOW BAT
CAUTION: Optional rechargeable stand-by batteries must match the power supply
output voltage setting.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
Divider
Power
Distribution
Module(s)
12VDC Rechargeable Battery
(optional)
SMP10C12Xseries