1 Source S1-TBEU22P7S Manuel d'instructions d'installation - Page 15

Parcourez en ligne ou téléchargez le pdf Manuel d'instructions d'installation pour {nom_de_la_catégorie} 1 Source S1-TBEU22P7S. 1 Source S1-TBEU22P7S 17 pages. Heat/cool & heat pump 7-day programmable digital thermostat

INSTALLATION INSTRUCTIONS
Test Operation
On the thermostat, press the Mode button
until COOL is displayed. Press the
COOLER or WARMER button until the set
temperature is 10 degrees below room
temperature. The HVAC unit should
energize in the cooling mode
Owner's Manual)
Note: You may need to wait up to five minutes
for cooling to energize due to the compressor
lockout feature.
TWO STAGE OPERATION - The 2nd stage
of cooling is turned on when the room
temperature is equal to or greater than:
the setpoint plus the 1st stage deadband
(one degree, adjustable), plus the 2nd
stage deadband (two degrees, non-
adjustable).
Heating
Deadband
db 2
(non-adj. 2 )
2nd Stage
1st Stage
turn on
turn on
On the thermostat, press the Mode button until
OFF is displayed. Press the Fan button until
Fan On is displayed. The fan should turn on
and run continuously.
.
Cooling
Deadband
Deadband
Deadband
db 1
db 1
db 2
(adj. 1-6 )
(adj. 1-6 )
(non-adj. 2 )
Heat or Cool
1st Stage
Setpoint
turn on
Page 15
S1-TBEU22P7S
(page 7 of the
2nd Stage
turn on