ALTUS Du350 Manuel du produit - Page 7
Parcourez en ligne ou téléchargez le pdf Manuel du produit pour {nom_de_la_catégorie} ALTUS Du350. ALTUS Du350 18 pages.
Duo Series
Doc. Code: CE113100
Fast Digital Outputs
Number of outputs
Maximum current per point
Output type
Maximum frequency of pulse
generation
Minimum pulse bandwidth
@ 24 Vdc
Status indication
Protection
Operation voltage
Insulation
Output impedance
Terminal block configuration
Output modes
Maximum number of used
outputs
Functions performed via
software
Access way to fast outputs
registers
Notes
Maximum current per point: the fast transistor output has no overload protection. If output protection is necessary external
fuse to the product should be used.
Functions performed via software: variation of 1 in 1 Hz or 1 in 1 % for frequency settings and duty cycle respectively.
ATTENTION:
During the product power on, fast outputs may change its state for approximately 100 us.
Altus S. A.
DU350, DU351
2 fast:
Q00 and Q01
0.5 A
Transistor ("Source" type)
50 kHz
Minimum external load
No load
1000
50
Through reserved fixed operands
TVS diode in all transistor outputs
10 to 30 Vdc
2000 Vac per one minute between each output group
2000 Vac per one minute between output group and logic circuit
700 m
Fast outputs are located in the connector of digital output insulation
group 0. The connector is made up of a terminal block for each
output, a terminal block to the common contact (power supply) and a
0 V terminal block reference.
Q00 to Q01 – fast output 0 to 1 of insulation group 0
C5 - Reference (0 V), insulation group 0 (shared with the relay
(DU351) / transistor (DU350) outputs)
C6 – Power supply, insulation group 0 (shared with the transistor
outputs (DU350)). Maximum voltage 30 Vdc
PTO, VFO and PWM
2
PTO
Writing of the value (number of
pulses) to be generated
Writing of the number of pulses
to be generated in the
acceleration / des-acceleration
Start / end of the outputs
operations
Fast outputs diagnostics
Monitoring of the current state of
fast outputs
In reserved fixed operands
DU350, DU351
Minimum pulse time
20 s
4 s
2 s
VFO/ PWM
Writing of the frequency value to
be generated in Hz (1 Hz to 50
kHz)
Writing of the outputs Duty-
Cycle from 0 to 100 %
Start / end of outputs operations
Fast outputs diagnostics
Revision: G
7