INSTALLATION
WARNING: check that the power sup-
ply is disconnected before carrying out
any procedures on the unit.
WARNING: the appliance must be fitted
according to the national regulations
on process plant engineering.
WARNING: electrical wirings, installation
of the fan coils and relevant accessories
should be performed by a technician
who has the necessary technical and
professional expertise to install, modify,
extend and maintain systems, and who
is able to check the systems for the pur-
poses of safety and correct operation.
INSTALLING THE UNIT
To install the unit, proceed as follows:
- Remove the air filter
- Remove the covering cabinet
- With wall-mounted units, keep a mini-
mum clearance of 80mm from the
floor. With floor-standing units on feet,
refer to the instructions supplied with
the accessory
- Use wall plugs (not supplied) for wall-
mounted installations
When using the support accessory (AMP
accessory), proceed as follows:
Assemble the 4 supports at the sides of
the device, inserting the upper tang in the
hole and fixing the lower part to the com-
ponent by means of the screws supplied.
Fix the flanges to the ceiling, using wall
plugs (not supplied); for the relative
positions between the flanges and the
component, refer to the size data
- Apply any accessories.
The VCF valve and the BC4 tray cannot
be installed at the same time on the
same fan coil.
M a k e t h e wa t e r c o n n e c t i o n s a s
described in the relative chapter.
Make the condensate discharge connec-
tion as described in the relative chapter.
WATER CONNECTIONS
- Make the water connections.
- In the event of disassembly and rein-
stallation, use new gaskets.
Refer to the size data for the position,
type and diameter of the water con-
nections.
You are advised to adequately insulate
water lines and/or fit the auxiliary
condensate drain tray (available as an
accessory), to prevent dripping during
WARNING: install a device, main
switch or plug which allows to com-
pletely cut off the power supply from
the unit.
Instructions which are essential for the
proper installation of the equipment are
given here.
The completion of all the operations
in accordance with the specific
requirements is however left to the
experience of the installation engineer.
The fan coil must be installed in such a
position that the air can be distributed
throughout the room and so that there
The fan coils that work in heat mode
only do not require condensate dis-
charge.
Make the electrical wiring as shown in
the relative chapter and in the wiring
diagrams.
Install and connect any accessories.
Complete the installation by reassem-
bling the casing and air filter.
Start up the fan coil and check all the
components and functions are operat-
ing correctly.
ZX
65 mm
the cooling function.
After installing, check the seal on the
connections.
are no obstacles (curtains or objects) to
the passage of the air from the suction
louvers.
The fan coil should be installed in such a
way as to facilitate routine (filter clean-
ing) and special maintenance opera-
tions, as well as access to the air drain
valve on the side of the unit frame
(connections side).