I.L. 29C508B
Source
L
C
Load
Figure 3-4 Connection Diagram
Figure 3-5 Rating Plug Installation
Effective 9/00
R
N
Grey
White
Make sure interphase barriers are properly seated in the
base and sliding handle barrier is properly seated in the
cover.
Install circuit breaker covers and pan-head
screws.Install the rating plug into the trip unit (Figure 3-5
and Table 3.1). The pins on the circuit board must line
up with the sockets in the rating plug and require only
minimal pressure to install. Do NOT attempt to force the
rating plug into the trip unit.
NOTICE
The pins on the circuit board are specifically cut,
and the sockets in the rating plug are specifically
filled to prevent an incorrect rating plug from being
installed.
Screw in and tighten the rating plug screw to secure the
rating plug.
Reset circuit breaker by moving handle to the reset
position. Move handle to the ON position. Circuit break-
er handle should remain at the ON position.
Press Push-to-trip button to check the manual tripping of
the circuit breaker.
4.0 PRINCIPLE OF OPERATION
In open air at 40°C, a L-Frame circuit breaker with a
Digitrip OPTIM 550 Trip Unit installed will carry continu-
ously up to 600 amperes without exceeding a 50°C rise
at the terminals. The calibration of the trip unit is insen-
sitive to ambient temperatures over a range of -20° to
+55°C. However the trip unit contains thermal tempera-
ture protection circuitry that initiates a trip operation for
self-protection if the internal ambient temperature at the
printed circuit board (PCB) reaches approximately
100°C. This may occur for open air temperatures above
40°C with circuit breaker currents near full load.
For ambient conditions above 40°C and where the maxi-
mum ampere rating plug has been installed, derating of
the circuit breaker frame should be considered to avoid
exceeding a safe terminal temperature operating range.
Consult Cutler-Hammer for recommendations.
4.1 GENERAL
The Digitrip OPTIM 550 Trip Unit provides a tripping sig-
nal to the flux transfer shunt trip when current and time
delay settings are exceeded. This is accomplished by
employing the Cutler-Hammer custom designed inte-
grated circuit Sµre™chip, which includes a microcom-
puter to perform its numeric and logic functions.
In the Digitrip OPTIM 550 Trip Unit, all required sensing
and tripping power to operate its protection function is
derived from the current sensors in the circuit breaker.
The secondary currents from these sensors provide the
correct input information for the protection functions, as
well as tripping power, whenever the circuit breaker is
carrying current. These current signals develop analog
voltages across the appropriate calibrating resistors.
Page 5