CVS Controls 1200 Manuel d'instruction - Page 3

Parcourez en ligne ou téléchargez le pdf Manuel d'instruction pour {nom_de_la_catégorie} CVS Controls 1200. CVS Controls 1200 11 pages. Pneumatic positioner

CVS Controls 1200 Manuel d'instruction

Installation

Linear:
1. Mount bracket with two 5/16"x1"
bolts to actuator. Leave bolts loose at
this point.
2. Mount positioner to bracket with
two 8mmx1-1/2 bolts and spacers.
Leave bolts loose at this point
3. Install threaded shaft into
connecting block.
4. Apply air to actuator until valve is
at 50%.
5. Using link bearings and link,
connect from threaded shaft to
positioner travel arm.
Note: Travel arm is metric.
6. Tighten link bearings to travel arm
with ¼" bolt and nut. Adjust nuts on
threaded shaft until link is parallel
with actuator. Then tighten.
7. Slide positioner until link is parallel
with actuator stem. Tighten bolts.
8. Adjust link so that the travel arm
forms a right angle to the actuator.
Tighten bolts.
9. Apply air to actuator until travel is
100%. Inspect to ensure travel arm is
not touching stopper on back side of
the positioner. If so, adjust link
bearing bolt on travel arm
accordingly.
10. Remove air from actuator and
inspect down travel stop. Adjust
accordingly.
3