AKO 55724 Manuel de l'utilisateur - Page 11
Parcourez en ligne ou téléchargez le pdf Manuel de l'utilisateur pour {nom_de_la_catégorie} AKO 55724. AKO 55724 16 pages. Gas leak detection alarm
7.- Operation
No alarms
The input indicators are green.
Pre-alarm / alarm activated
The station emits an audible alarm sound, shows the affected input(s) in red, the general alarm indicator illuminates
and the visual alarm flashes.
Wiring error / malfunction
The station emits 3 short beeps every two minutes and the affected input indicator flashes red.
Short-circuit detection in an input
If a short-circuit is detected in any given input, this input will be deactivated and the indicator corresponding to the
affected input will flash red. The general alarm indicator will also flash.
Once the problem has been resolved, to re-establish functioning of the affected input, press the Mute button for
more than 1 second.
MUTE Function
Allows for sound to be silenced in the event of a gas pre-alarm or alarm. Does not affect relay or indicator
functioning.
To activate it, press the Mute button at any point when the pre-alarm or alarm is activated. The display shows the
silenced alarm indicator
Optionally, it can also be remotely activated using a push-button connected to digital input 1 (DI1).
If a pre-alarm is silenced, this function will be voided by changing to an alarm or if a new pre-alarm or alarm is
activated.
Saved Alarms
Indicator
flashes green to indicate that a gas pre-alarm or alarm has sounded in our absence. To delete it,
press the mute button.
Set Hold Mode
Avoid false alarms during the chamber charging or cleaning process.
When this mode is activated, pre-alarms will not sound and alarms will sound like pre-alarms to all effects (sound,
relay and signal activation).
To activate / deactivate it, press the Mute key for 3 seconds; the display will indicate indicator
Optionally, it can also be remotely activated / deactivated using a switch connected to digital input 2 (DI2).
This mode will remain activated for a maximum of 5 hours, before automatically deactivating itself.
If it is activated using the Mute key, it can only be deactivated using the same key. The same applies to
activation using digital input 2.
Maintenance Mode
Disables the gas pre-alarms and alarms for 1 hour for maintenance tasks
When it is activated, no gas pre-alarm or alarm will sound.
To activate / deactivate it, press the Mute key for 6 seconds; indicator
.
11
.
will flash.
5572H402 Ed.03