AKO AKO-D1461 Series Instructions d'installation

Parcourez en ligne ou téléchargez le pdf Instructions d'installation pour {nom_de_la_catégorie} AKO AKO-D1461 Series. AKO AKO-D1461 Series 2 pages.

Warnings
-Using the equipment without following the manufacturer's instructions may affect the device's safety requirements. To ensure that the
device operates correctly, only probes supplied by AKO should be used.
-The unit must be installed in a location protected from vibrations, water and corrosive gases, where the ambient temperature does not
exceed that shown in the technical data.
-To ensure a correct reading, the probe must be situated in a location without any external heat influences except for the temperature which
is being measured or controlled.
-The power supply circuit must be provided with a main switch rated at at least 2 A, 230 V, located close to the equipment. The cables will
enter through the back and should be type H05VV-F or H05V-K.
-The gauge will depend on local regulations, but should in no case be less than 1 mm .
-Connecting wires for the relay contacts should be sized 2.5 mm .
-Between -40 ºC and +20 ºC, if the probe NTC is prolonged till 1.000 m with a mínimum of cable 0,5 mm², the maximum deviation will be of
0,25 ºC (extension cable for probe ref. AKO-15586)
NOTE: Equipment not compatible with AKO-14917 (external communication module) and AKO-14918 (programming key)
Installation
1
Operation
GB
1461H032 Ed.01
Installation instructions
Press for 5 seconds, allows changing the set point (SP). (Not available in thermometers)
SET
Pressing for 10 seconds goes to the programming menu.
In the programming menu, go to the level displayed or accept the new value while setting a parameter.
Pressing for 5 seconds starts/stops defrosting. (Not available in thermometers)
SET
The programming menu, allows you to scroll through the various levels or, during the setting of a parameter, to change the value.
Press for 5 seconds to start/stop Fast Freezing mode (rapid cooling). (Function available depending on the model).
SET
The programming menu, allows you to scroll through the various levels or, during the setting of a parameter, to change the value.
Pressing for 5 seconds activates Standby mode, pressing for 2 seconds returns the equipment to normal mode. In Standby
SET
mode, the equipment performs no actions and only the indicator is displayed on the screen m.
In the programming menu, go to the level displayed.
Pressing it for 1 second, activates or deactivates the cold room light (if P6=3). This function stays active although the unit is
AKO-D1460x
AKO-D1461x
AKO-D1462x
SET
in the stand-by mode. (Function available depending on the model).
AKO-D1463x
AKO-D1464x
AKO-D146xx-C
In the programming menu, exit without saving parameter, return to previous level or exit programming.
2
2
2
2
ø max. 3,7
2
4
3
35
125,5
171
COOL relay ON
ECO mode ON
Display
Program Mode
Stand-by mode ON
Keyboard
Fast Freezing mode ON
1
:In AKO-D1461x / D1462x, if P0=0
2
:In AKO-D1461x / D1462x, if P0=1
Wiring
The probe and its cable should NEVER be
installed in the same conduit as power,
control or supply cables.
AKO-D1460x
S1
AKO-D14601:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14602:
230 V~ ±10%
50 / 60 Hz
AKO-D1461x
Mode: COLD
(P0=0)
S1
AKO-D14610:
230 V~ ±10%
50 / 60 Hz
AKO-D14612:
120 V~ +8% -12%
16 A
50 / 60 Hz
COOL
N
I max.:
16 A
L
AKO-D1461x
Mode: HEAT
(P0=1)
S1
AKO-D14610:
230 V~ ±10%
50 / 60 Hz
AKO-D14612:
16 A
120 V~ +8% -12%
1
50 / 60 Hz
FAN relay ON
DEF relay ON
RES
Light ON /
2
RES relay ON
N
I max.:
16 A
L
AUX relay ON
AKO-D1463x
S3 / DI2
DI1
S2
S1
AKO-D14631:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14632:
230 V~ ±10%
50 / 60 Hz
AKO-D14632-C:
16 A
90-240 V~
50 / 60 Hz
8 A
DEF
16 A
COOL
1
2
FAN
N
I max.:
Modbus*
16 A
L
AUX Relay
S1: Probe 1, temperature in the chamber or cabinet.
Function as per
S2: Probe 2, defrost.
AUX.
parameter P6
S3: Probe 3, temperature of product / 2nd defrost.
DI1/DI2: Digital Input 1 / Digital Input 2.
AKO-D1462x
Mode: COLD
DI2
(P0=0)
DI1
S1
AKO-D14621:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14622:
230 V~ ±10%
50 / 60 Hz
AKO-D14622-C:
16 A
90-240 V~
50 / 60 Hz
ALARM
COOL
6 A
1
2
3
N
I max.:
16 A
L
Modbus*
GSM ALARM
AKO-52042
AKO-D1462x
Mode: HEAT
DI2
(P0=1)
DI1
S1
AKO-D14621:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14622:
230 V~ ±10%
50 / 60 Hz
AKO-D14622-C:
16 A
90-240 V~
50 / 60 Hz
ALARM
RES
6 A
1
2
3
N
I max.:
16 A
L
Modbus*
GSM ALARM
AKO-52042
AKO-D1464x
S3 / DI2
DI1
S2
S1
AKO-D14641:
120 V~ +8% -12%
50 / 60 Hz
AKO-D14642:
230 V~ ±10%
50 / 60 Hz
AKO-D14642-C:
16 A
90-240 V~
50 / 60 Hz
8 A
DEF
16 A
COOL
6 A
3
1
2
3
FAN
AUX.
AUX
N
I max.:
Modbus*
16 A
L
* Depending on model
Start-up
AKO-D1461x / AKO-D1462x
On power-up, the equipment will start up in Wizard mode (InI / 1
flashing), press N or Q to select the most appropriate
application and press SET.
1: Chilling
2: AC
3: Heat/Incubators
The wizard will configure the parameters of the equipment for the
chosen application (see table).
WIZARD
SP
d0
d1
P0
InI=1: Chilling
0
6
20
0
InI=2: AC
21
0
0
0
InI=3: Heat/Incubators
37
-
-
1
AKO-D1463x / AKO-D1464x
On power-up, the equipment will start up in Wizard mode (InI / 1
flashing), press N or Q to select the most appropriate application
and press SET.
1: Chilling
2: Frozen
3: Fruits and vegetables
4: Fresh fish
5: Soft Drinks
6: Bottle racks
7: AC
The wizard will configure the parameters of the equipment for the
chosen application (see table).
WIZARD
SP
d0
d1
F0
F3
InI=1: Chilling
2
4
20
8
1
InI=2: Frozen
-18
4
20
0
0
InI=3: Fruits and Vegetables
10
4
20
30
1
InI=4: Fresh fish
0
4
20
8
1
InI=5: Soft Drinks
3
24
20
8
1
InI=6: Bottle racks
12
24
20
30
1
InI=7: AC
21
96
0
99
1
WARNING: The default parameters by type of
application have been defined for the most common
applications. Check that these parameters are suitable
for your installation.