MODEL CXLdp HIGH ACCURACY
DIFFERENTIAL PRESSURE TRANSDUCER
INSTALLATION & MAINTENANCE SHEET
WARNING! READ
BEFORE INSTALLATION
1. GENERAL:
A failure resulting in injury or damage may be
caused by excessive overpressure, excessive
vibration or pressure pulsation, excessive
instrument temperature, corrosion of the pres-
sure containing parts, or other misuse. Con-
sult Ashcroft Inc., Stratford, Connecticut, USA
before installing if there are any questions or
concerns.
2. OVERPRESSURE:
Pressure spikes in excess of the rated overpres-
sure capability of the transducer may cause irre-
versible electrical and/or mechanical damage to
the pressure measuring and containing elements.
3. STATIC ELECTRICAL CHARGES:
Any electrical device may be susceptible to dam-
age when exposed to static electrical charges.
To avoid damage to the transducer the
operator/installer should follow proper ESD
(electrostatic discharge) protection procedures
before handling the pressure transducer.
DESCRIPTION
The Ashcroft
®
Model CXLdp High Accuracy is a
low differential pressure transmitter to be used on
clean, dry, non-corrosive gases. It is available in
two accuracy classes and its performance is trace-
able to the U. S. National Institute of Standards and
Technology (NIST). The 3 located in the third posi-
tion distinguishes a 0.25% transmitter. Both unidi-
rectional (e.g. 0 to +1.0 IW) or bi-directional (e.g.
±2.0 IW) models are available. A green LED located
on the front of the transmitter indicates power and
operational status. The LED light intensity increases
as pressure increases.
SPECIFICATIONS
Accuracy:
• ±0.25% span
- (±0.04mA for 4-20mA output units)
- (±0.025V for 0-10Vdc output units
Output Signal: Specified at time of order.
• 4-20ma (For symmetric bidirectional ranges
0IW= 12mA
or
• 0-10Vdc; 0-5Vdc User selectable option (For
symmetric bidirectional ranges 0IW= 5 or
2.5Vdc respectively).
Supply Voltage:
• 4-20mA: 12-36 Vdc (no regulation required)
(see Figure 1)
or
• 0-10Vdc (0-5Vdc User selectable option):
14-36 Vdc or 24 Vac (+/- 20%)
• Supply Current: 6mA (4.5mA for 5Vdc
output option)
Reverse Wiring Protected
Electrical Connection: unpluggable terminal block
accepts 12-26 AWG
Operating Temperature: 0-160°F
© 2014 Ashcroft Inc. 250 East Main Street 06614, Tel: 203-378-8281 • Fax: 203-378-0499, All specifications are subject to change without notice.
All sales subject to standard terms and conditions. www.ashcroft.com All rights reserved. I&M011-10137 11/14
Load Limitations 4-20mA Output
Figure 1
Loop Resistance (Ω)
TING
V min = 12V+ [.022A*(R L )]
*includes a 10% safety factor
R L = R S + R W
R L = Loop Resistance (ohms)
R S = Sense Resistance (ohms)
R W = Wire Resistance (ohms)
Loop Supply Voltage (Vdc)
* F.S. pressure is equivalnt to the span of the transmitter (16mA).
Enclosure:
NEMA 1 Fire-retardant ABS Meets UL 94-5VA
Weight: Approx. 2.5 oz.
Pressure Connection Options:
1
˝ Brass Barbs or
4
1
NPT Female Brass
8
Figure 2
Optional:
1
˝ conduit
2
or plenum mounting
bracket and cover
available as sepa-
rately ordered kit –
part number
101A213-01.
(see Figure 2)
INSTALLATION
Mounting:
The transmitter
Figure 3
can be mounted
or
Use
on a 35 mm DIN
#10
rail or with #8 or
screw
#10 screws using
the 4 mounting
holes provided.
Torque limits on
the mounting
holes provided is
Zero Pot
6 inch-pounds.
(see Figure 3)
Electrical Wiring:
1. The use of sheilded cable is recommended for
optimum performance. Connect the shield to the
guard terminal on the reading instrument (meter,
etc.) if available or to ground.
2. Remove the terminal block on the front of the
transmitter.
3. Available electrical versions are:
a.) CURRENT 4-20mA; black terminal block.
b.) VOLTAGE 0-5Vdc/0-10Vdc; green terminal
block.
Follow the terminal block label markings on
the CXLdp High Accuracy to identify the
terminals;
• 4-20mA Ouput: The left, negative (–), and
right, positive (+) terminals are used, ignore
the center terminal which is not used. Con-
nect the power supply positive lead to the
CXLdp High Accuracy positive terminal, con-
nect the negative power supply lead to the
negative terminal of the BCS 4-20mA input.
ZERO
Zero adjust
potentiometer
Last, connect the (–) negative terminal on the
CXLdp High Accuracy to the (+) positive BCS
input.
ZERO
Zero adjust
potentiometer
Common (V
)
POWER SUPPLY
• 0-10Vdc; 0-5Vdc Output: Follow label mark-
ings for terminal assignments; COM is for
Common (supply and output negative), V
is for supply positive and V
signal. The CXLdp High Accuracy Voltage Out-
Use #8
screw
put unit is supplied as standard with 0-10 V
output, to convert to 0-5 V output see
following instructions.
- 0-10 Vdc Output: Product is supplied as
standard with 0-10 V output, see instruction
below to access the Voltage Output jumper.
Green LED
- 0-5 Vdc Output: See below for proper
jumper selection. To convert the unit from a
0-10 V output to a 0-5 V output unit note the
following. Access the jumper by simultane-
ously pushing both housing tabs away from
the housing, see drawings under "General
Dimensions" for
details. Change
jumper (orange)
into position as
shown below,
carefully reattach
housing cover.
When finished
mark check box
on front label in-
dicating that the
unit now provides
a 0-5Vdc output.
4. Firmly reinstall the terminal block plug to its
mating connector.
SPAN
+
Span adjust
potentiometer
+
POWER
+
SUPPLY
BCS
SPAN
Span adjust
potentiometer
V
+
Out
Vin (V+, Supply)
IN
is for output
OUT
Figure 4
Jumper
0-10 Vdc
(orange)
0-5 Vdc
Label Part No. 238A713-01