Function
Behaviour with internal device faults
If internal device faults were detected during the test function, the status LED
flashes permanently red. The indicator relay K2 switch to the alarm state.
Behavior on faulty connection
When detecting broken wire on terminals L(+)/L(-), the measurement is
disabled. The reaction time could be up to 2 min. The monitoring relay K2
goes in alarm state, the status LED shows flash code 1 in red colour. After
removing the interruption the fault is automatically reset (max. reaction time
up to 2 min) and the measurement of the insulation resistance is continued.
Stored alarm values remain stored. An interruption of the protective earth
connections PE1/PE2 causes the same reaction as interrupting the
measuring circuit, only the status LED shows flash code 2 in red colour.
Behaviour at parameter failures
With wrong settings on the rotary switches the device goes to failure mode.
The indicator relay K2 changes to alarm state and the status LED shows
the red flash code 3.
External control input
To terminals X1/X2 an external combined Test-/Reset button can be
connected. If the terminals X1/X2 are bridged for approx. > 1.5 s and
< 10 s the test mode is started. This has the same function as pressing the
internal test button. When bridging X1/X2 for < 1.5 s, a stored alarm will
be reset. This has the same function as pressing the internal reset button.
If X1/X2 is activated for > 10 s, the measuring function is stopped.
The measuring function remains suspended for the duration of the control
of X1/X2.
Connection of an external coupling device
An external coupling device RP 5898/240 can be connected to extend the
input voltage range of the monitored voltage system on RN 5897/240. The
terminals with the same legend of the insulation monitor and the coupling
device RL 5898 or RP 5898 (VSG1, VSG2, L(+), L(-)) are connected together.
The network to be monitored is connected to terminals L1(+) und L2(-) on
the coupling device. Using the rotary switch "Rel./VSG" the connection
of the coupling device has to be selected and activated. The broken wire
detection is active on the terminals L1(+)/L2(-) on the coupling device.
A broken wire between coupling device and insulation monitor cannot be
detected immediately but the measured values on interruption of 1 or 2
wires between coupling device and insulation monitor are much lower as
the real values, which will cause an early response of the device.
Programming/setting of parameters/set-up of the insulation monitor
All settings are made via 3 rotational switches on the front of the device.
To avoid unauthorised manipulation of the settings, the unit has a sealable
transparent cover on the front.
The response value for Alarm is adjusted by the first rotary switch "R
The second rotary switch "Rel./VSG" is used to alter the relay function as
well as for activation/deactivation of the VSG. If set to "n.c." the output is
de-energized on trip, If set to "n.o." the output is energized on trip. The
VSG is activated in the "on" position and deactivated accordingly in the
"off" position. In addition this rotary switch has 2 sections. If the setting is in
the section, the broken wire detection in the measuring circuit is activated,
if the setting is on the second section, the broken wire detection in the
measuring circuit is de-activated.
The third rotational switch selects "UN" selects the voltage system connection
and manual or auto reset it has also 2 sections. In section one the unit is
on auto reset, in section 2 it is on manual reset. Changes of the setting the
unit accepts immediately without restart.
If the second or third rotary switch is in an undefined position, the unit
changes to "parameter failure" (see description under "behaviour at
parameter failures").
Function Diagram
U H
R
E
Earth fault
R
A
Hysteresis function
11-14
Open circuit operation
11-12
11-14
De-energized on trip
11-12
Manual reset
Reset
11-14
Open circuit operation
11-12
11-14
De-energized on trip
11-12
Semiconductor Output (PWM output)
0
5ms
Minimum pulse length 5ms (corresponds to 5k )
0
1000ms
Pulse length 1000ms (
corresponds to
0
2000ms
Maximum pulse legth 2000ms (
".
A
Broken wire detection:
Short circuit detection:
Flashing Codes Status LED
Measuring function
disabled
Self test
Extended
test
Internal
system error
Connection failure
measuring ciruit L(+)/L(-)
Connection failure
protective conductor PE1/PE2
Parameterization
error
3
3000ms
3000ms
1M )
Pulse break
min. 1s
3000ms
corresponds to
2M )
M12318
If the PWM-signal is continuously high,
a broken wire is detected.
If the PWM-signal is continuously low, the
semiconductor may have a short circuit.
t
t
M12292
t
M12295