DOLD RN 5883 Installations - Page 3

Parcourez en ligne ou téléchargez le pdf Installations pour {nom_de_la_catégorie} DOLD RN 5883. DOLD RN 5883 8 pages. Residual current monitor, type b for ac and dc systems

Technical Data
Input
Auxiliary voltage U
:
H
Voltage range
at U
= AC/DC 24 ... 80 V:
H
at U
= AC/DC 80 ... 230 V:
H
Nominal frequency U
:
H
Nominal consumption
at AC:
at DC:
Measuring range:
Measuring range
fine adjustment:
Überlastbarkeit:
Alarm:
Pre-alarm:
Frequency range:
Repeat accuracy:
Temperature drift:
Reaction time:
Switching delay
Pre-alarm / alarm:
Output
Contacts:
Thermal current I
th
up to 30 °C:
up to 40 °C:
up to 60 °C:

Switching capacity

at AC 15:
NO contact:
NC contact:
Electrical life
to AC 15 at 1 A, AC 230 V:
Short circuit strength
max. fuse rating:
Mechanical life:
Analogue Output (option)
Terminal U+ / U-:
General Data
Operating mode:
Temperature range
Operation:
Storage:
Altitude:
Insulation coordination
according to IEC 60664-1:
RN 5883 cennected with
current transformer ND 5015, ND 5018
Rated impuls voltage /
pollution degree:
Auxiliary voltage / Meas. circuit: 6 kV / 2
Auxiliary voltage / Contacts:
Auxiliary voltage / Analoge output: 6 kV / 2
Contacts / Analoge output:
Meas. circuit / Analoge output:
Contacts 11,12,14 / 21, 22, 24: 4 kV / 2
AC/DC 24 ... 80 V, AC/DC 80 ... 230 V
DC 19 ... 110 V, AC 19 ... 90 V,
DC 64 ... 300 V, AC 64 ... 265 V
AC 50 / 60 Hz
5 VA
2.5 W
10 ... 100 mA, 30 ... 300 mA,
100 ... 1000 mA, 300 ... 3000 mA
(3 ... 30 mA on request)
1 ... 10
with overload protection
100 % of the adjusted measuring range
10, 20, 30, 40, 50, 60, 70, 80, 90, 100 %
of the adjusted alarm value
DC and AC to 250 Hz*
)
*
)
depending on the differential current
transformer used. See „Function" Table 1.
≤ ± 3 %
≤ ± 0.1 % / K
300 ms
0 ... 10 s
1 changeover contact for pre-alarm,
1 changeover contact for alarm
5 A
4 A
2 A
3 A / AC 230 V
IEC/EN 60947-5-1
1 A / AC 230 V
IEC/EN 60947-5-1
3 x 10
5
switch. cycl.
IEC/EN 60947-5-1
4 A gG / gL
IEC/EN 60947-5-1
≥ 10
8
switching cycles
0 ... 10 V; 5 mA
variant RN 5883/_ _1
Screened wire; screen one end grounded
at device to PE
Continuous
- 40 ... + 60°C
- 20 ... + 60°C (variant /_1_ and /_2_)
- 40 ... + 70°C
< 2000 m
6 kV / 2
6 kV / 2
6 kV / 2
Technical Data
EMC
Surge voltages:
Electrostatic discharge:
HF irradiation
80 MHz ... 2,7 GHz:
HF-wire guided:
Fast transients:
Surge voltages:
Interference suppression:
Degree of protection
Housing:
Terminals:
Housing:
Vibration resistance:
Climate resistance:
Terminal designation:
Wire connection:
Fixed screw terminals
Cross section:
Stripping length:
Wire fixing:
Fixing torque:
Mounting:
Weight:
Dimensions
Width x height x depth:
UL-Data RN 5883
These devices only monitor residual currents and are not intended to
be used as Ground Fault Circuit Interrupter (GFCI) in accordance with
UL1053 / UL943.
These devices have been investigated to be used with external differen-
tial current transformers manufactured by E. Dold & Söhne KG, Cat. Nos.
ND5015/024/61, ND5015/035/61 or ND5015/070/61.
Supply voltage U
:
N
Switching capacity relays
Ambient temperature 30°C:
Ambient temperature 40°C:
Ambient temperature 60°C:
Analogue output
(only at variant/__1):
Max. measuring frequency:
Wire connection:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo
3
Class 3 (5 kV / 0.5 J) DIN VDE 0435-303
8 kV (air)
IEC/EN 61000-4-2
20 V / m (class 3)
IEC/EN 61000-4-3
10 V (class 3)
IEC/EN 61000-4-6
2 kV (class 3)
IEC/EN 61000-4-4
1 kV class 3)
IEC/EN 61000-4-5
Limit value class B
EN 55011
IP 30
IEC/EN 60529
IP 20
IEC/EN 60529
Thermoplastic with V0-behaviour
according UL subject 94
Amplitude 0.35 mm
frequency 10 ... 55 Hz IEC/EN 60068-2-6
40 / 60 / 03
IEC/EN 60068-1
EN 50005
DIN 46228-1/-2/-3/-4
0.5 ... 4 mm² (AWG 20 - 10) solid or
0.5 ... 4 mm² (AWG 20 - 10)
stranded wire without ferrules
0.5 ... 2.5 mm² (AWG 20 - 10)
stranded wire with ferrules
6.5 mm
Cross-head screw / M3 box terminals
0.5 Nm
DIN rail
IEC/EN 60715
approx. 160 g
52.5 x 90 x 71 mm
AC/DC 24-80V single or double phase
50/60 Hz;
AC/DC 80-230V single or double phase
50/60 Hz
5A, 250Vac G.P.
250 Vac, 2A pilot duty
250 Vac, 1/2hp
4A, 250Vac G.P.
250 Vac, 2A pilot duty
250 Vac, 1/2hp
2A, 250Vac G.P.
0 .. 10V, 5mA
DC, AC (0 – 250Hz)
AWG 20 - 12
60°C / 75°C copper conductors only
04.03.20 en / 201A