CONNECTIONS
NOT-DOLPROHD-00
Identification
Functions
L
AC mains power phase, max.
10mm² (wire colour code: brown or
black)
N
AC mains power neutral, max.
10mm² (wire colour code: blue,
white or red)
AC mains power earth, max.
10mm² (wire colour code: green/
yellow or green)
-DC
Battery negative (common), pin M8
(wire colour code: black)
+DC1
Main battery positive, pin M8 (wire
colour code: red)
+DC2
Auxiliary 2 battery positive, pin M8
(wire colour code: red)
+DC3
Auxiliary 3 battery positive, pin M8
(wire colour code: red)
CHARGE
Curve and battery charge mode
SELECT
selector, 10 positions (0 to 9)
BATTERY FUSES
Battery protection fuses (on the
–DC supply)
EXT TOUCH
CAN bus for TOUCH screen con-
nection
EXT COM1
CAN bus for network operation
& COM2
ID SELECT
Configuration charger ID (network
operation)
TEMP SENSOR
Battery temperature sensor
(2 wires no polarity, no direction)
RELAY
Alarm dry contact
CONNECTIONS
NOT-DOLPROHD-00
AC CABLES AND CIRCUIT BREAKER
AC wiring
Check that cables are properly connected and
that the connections are tight.
For the mains power supply, it is preferable to use
an industrial cable, type HO7RNF. Observe the
recommendations below.
230VAC 50Hz
Charger rating
Length < 5m (16ft)
24V 40A
2.5mm² / AWG13
24V 60A
2.5mm² / AWG13
24V 100A
4mm² / AWG11
AC circuit breaker
The AC mains power line must have an on/
off switch with integral differential protection,
to protect persons, notably in cases of electric
shock.
Circuit breaker sensitivity must be 30mA. The
circuit breaker current rating must correspond to
the charger consumption. For this, observe the
recommendations below.
Mains power 230V
Charger rating
50Hz
24V 40A
8A – 30mA
24V 60A
10A – 30mA
24V 100A
20A – 30mA
Nota : The charger has an internal protection fuse
on access L, which notably protects against a
general fault on the electronics board. As the fault
concerned is permanent, this fuse is not accessible for
maintenance.
115VAC 60Hz
Length < 5m (16ft)
4mm² / AWG11
4mm² / AWG11
6mm² / AWG9
Mains power 115V
60Hz
16A – 30mA