Selecting CO
Settings
2
CO
ppm Setting:
To select the CO
2
Setting" button. The current setting will be displayed. Use the UP and
DOWN arrow buttons to adjust the setting. Press "Enter/Reset" to accept
the new setting.
CO
Deadband:
To select the CO
2
"Deadband" button under "CO
to adjust the setting. Press "Enter/Reset" to accept the new setting.
Locking Temperature/Humidity Functions
The temperature and humidity functions may be set to operate locked
("connECt") or split ("SPLit"). Press "Temp/Humidity Lock" to display the
current setting. Use the UP and DOWN arrow buttons to select a new
setting. Press "Enter/Reset" to accept the new setting.
• Select "connECt" if using only ventilating fans for cooling and
removing humidity. The fan will turn on when the sensor detects an
increase above the set-point in either humidity or temperature.
• Select "SPLit" if using a ventilating fan or AC unit for cooling and a
dehumidifier for removing humidity. The cooling device will turn
on when the temperature rises above the set-point, and the
dehumidifier will turn on when the humidity rises above the set-point.
• Select "SPLit" if using a fan or AC unit for cooling and a humidifier for
adding humidity. The cooling device will turn on when the temperature
rises above the set-point and the humidifier will turn on when the
humidity drops below the set-point.
Locking Temperature/CO
The temperature and CO
functions may be set to operate locked
2
("connECt") or split ("SPLit"). Press "Temp/CO
current setting. Use the UP and DOWN arrow buttons to select a new
setting. Hold "Enter/Reset" for 3 seconds to accept the new setting.
• Select "connECt" if using ventilating fans for cooling and a
compressed CO
setup. The CO
2
are activated, allowing the fans to exchange air while minimizing loss
of CO
.
2
• Select "SPLit" if using a recycling air conditioner for cooling and a
compressed CO
setup. The air conditioner and compressed CO
2
be activated independently.
• Select "SPLit" if using ventilating fans for cooling and a CO
generator. The ventilation fans and CO
activated independently.
• Select "connECt" if using a recycling air conditioner and a CO
generator. The CO
generator will be deactivated while the air
2
conditioner is operating to reduce the amount of heat the air
conditioner must offset.
Displaying Recorded Values
Press the "Min/Max Recall" button to display the minimum and maximum
recorded values for temperature, humidity and CO
button repeatedly to cycle through the values in the following order: max.
temperature, min. temperature, min. humidity, max. humidity, min. CO
max. CO
. Press "Enter/Reset" to reset a displayed value.
2
Fuzzy Logic Mode
Fuzzy Logic mode counters rising or falling CO
activating the CO
solenoid valve, allowing CO
2
more precisely. This function can be used only with compressed CO
Do not use Fuzzy Logic with a CO
Hold "Enter/Reset" for 5 seconds to activate or deactivate Fuzzy Logic
mode. Use the UP and DOWN arrow buttons to choose between Fuzzy
Logic mode ("LogIcon") if using compressed CO
("gEnErAt") if using a CO
generator. Press "Enter/Reset" to accept the
2
new setting.
ppm set-point, press the "ppm
2
deadband set-point, press the
2
." Use the UP and DOWN arrow buttons
2
Functions
2
Lock" to display the
2
will be deactivated when the fans
2
generator will be
2
level. Press the
2
levels by quickly
2
levels to be controlled
2
generator.
2
and generator mode
2
Calibrating the CO
• Place the Controller and sensor outdoors in a shaded area.
Note: If the unit is calibrated in a high-traffic or highly populated
area, a slightly higher calibration value of 400-475 ppm
is recommended.
• Plug in the Controller and allow it to warm up for a minimum of
30 minutes but 1 hour is recommended.
• Press the "Calibrate CO
calibration. Do not breathe on the unit while the calibration
function is activated.
• Press "Enter/Reset" to start the calibration sequence. "Co2_
CAL" will be displayed and the CO
• When it is complete, the screen will display normal functions.
Calibration will not affect any other settings. Note: It may take up
to 10 minutes to complete the calibration process.
FAQ
• How can I tell if the CO
Check the calibration of the CO
sensor outdoors for 30 minutes. The reading should be
about 380 ppm. If not, see the "Calibrating the CO
Sensor" section.
• What if the temperature reading is high?
Verify the remote sensor is not in a location with direct,
intense exposure to light.
• Do the humidity and temperature sensors need to
be calibrated?
No. The humidity and temperature sensors are digital and
do not require calibration.
Troubleshooting
• Why does the display read "Err SEn"?
The remote sensor is not connected or not
communicating with the controller. Verify the cable is
connected and the remote sensor is powered.
will
2
• Why are the small error LEDs illuminated?
2
The sensor or a connected device is malfunctioning. See
the "Error LEDs" section for more information.
2
• Why isn't the CO
Verify the correct CO
the "Daytime mode (photocell)" is illuminated.
• Why isn't the Controller powering the
connected devices?
Reset the circuit breaker. Ensure the device to be controlled
is working correctly by plugging the device into a reliable
power source. Verify the Controller is being supplied the
,
2
correct voltage.
Optional PC Connection
Downloadable software and a USB connection cable (available
separately) may be used to change the Controller's settings, verify
outputs are operating, and record and chart conditions in the growing
.
2
area using a personal computer. Download the necessary software
and instructions at www.Sunleaves.com.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Sensor
2
Sensor" button to activate automatic
2
calibration LED will blink.
2
reading is accurate?
2
sensor by placing the
2
output being activated?
2
mode has been selected and verify
2
2