7.11 Measurement duration 'C'
This parameter is responsible for the refresh rate of the LED display and value on 4..20 mA current
output. When this parameter is set, the module has to be restarted. It is possible to change the value
from 0.1 to 1 s, every 0.1 s.
8. Measurement parameter configuration
Measurement parameter configuration is set by proper set-up of configuration switches SW1 and
SW2. Description of switches SW1 and SW2 is presented in the following table and Figure 8-1:
SW 1
S1 – ON, HPF =10 Hz (OFF = 3 Hz)
S2 – range 100
S3 – range 10
S4 – range 25
S5 – DX: LPF = 1 kHz
S6 – LPF = 10 kHz
S7 – acceleration
S8 – velocity
12
Functions of configuration switches
S1 – ON, range 10 (OFF, range 100)
S2 – ON, range 25 (OFF, range 100)
S3 – ON - acceleration (OFF - velocity)
S4 – ON - RMS (OFF - PEAK)
S5 – ON, internal power supply +24 V for 4..20 mA
S6 – ON, external power supply for 4..20 mA
SW2