ULTRASONIC GUARDIAN BUNG DISTANCE
ULTRASONIC GUARDIAN INSTALLATIONS
"A" is NOT a good installation, since the bung opening is less than 1/3 the tank diameter away from the edge of the tank. In this
example, a Differential Pressure Guardian will have to be used instead of the Ultrasonic Guardian.
"B" is a GOOD installation. The bottom of the Guardian is into the tank, and the Guardian is mounted plumb and close to the
center of the tank.
"C" is NOT a good installation, since the Guardian cannot be mounted plumb. In this type of installation, the ultrasonic signal
will not bounce directly from the product back to the sensor, but will instead bounce around the inside of the tank, causing
inaccurate or even no reading. In this example, a Differential Pressure Guardian will have to be used instead of the Ultrasonic
Guardian.
Note: For installation geometry other than those shown, contact FLO-CORP customer service.
Once the bung opening is verified to be a good Ultrasonic installation, ensure the bung threads have not been compromised.
The Ultrasonic Guardian is now ready to be placed into service.