Domus Ventilation CMX-MULTI Panduan Petunjuk Instalasi - Halaman 4

Jelajahi secara online atau unduh pdf Panduan Petunjuk Instalasi untuk Kipas angin Domus Ventilation CMX-MULTI. Domus Ventilation CMX-MULTI 6 halaman. Mechanical extract ventilation

Domus Ventilation CMX-MULTI Panduan Petunjuk Instalasi
5
System Illustration
With 204x60mm spigots, the
CMX-MULTI units can support
direct duct runs, without the need
for adaptors or flexible duct fixings.
5.2
Ducting attached to the appliance must be supported adjacent to
the appliance using 522 Support clips. This is important for major
maintenance or end of life replacement to ensure that the ducting is
adequately supported if the CMX-MULTI / CMX-MULTI-H body is
removed.
5.3
Where ducting passes through unheated areas and voids (e.g. loft
spaces) it must be insulated in order to comply with Approved
Document F of The Building Regulations.
5.4
When passing through a fire-stopping wall or fire-compartment wall,
FireBrake intumescent duct connectors should be used in order to
comply with Approved Document B of The Building Regulations.
5.5
Alternative proprietary fire-stopping methods may be employed
provided they comply with Approved Document B of The Building
Regulations.
5.6
Rigid ducting – install using the least number of fittings to minimise
resistance to airflow. All duct runs should be as short and as straight as
possible for maximum performance.

6.0 Unit Wiring

6
LAB1356R | NoVEmBER 2018
5.7
Domus Ventilation Sound Attenuators 5SL-500 can be installed directly
on to the unit without the need for transformation connectors.
5.8
The stale extract air must be expelled to the exterior of the property. If
expelled through a wall, an airbrick should be fitted. If expelled through
the roof a universal roof terminal should be fitted or a proprietary roof
terminal designed for mechanical ventilation with a free area of at least
15175mm².
5.9
Further details regarding installation can be found in the 2010 Domestic
Ventilation Compliance Guide.
5.10
WARNING: This appliance must be earthed.
5.11
Important: All wiring must be carried out by a qualified
electrician and conform to the prevailing national regulations, for
example the latest edition of BS7671: IEE Wiring Regulations.
5.12
This appliance is suitable for 230V 50Hz single phase supply only, fused
at 3 Amps.
5.13
A double-pole switch having a minimum contact separation of 3mm
must be used to provide isolation for the appliance.
5.14
External isolators to be supplied by others.
Wire to CMX-MULTI
L - Live(Brown)
N - Neutral(Blue)
E- Earth(Green/Yellow)
SL1 - Boost Switch Live (Grey)
SL2 - Purge Switch Live (Black)
PAGE 4