Donaldson Torit Delta P Plus Panduan Instalasi dan Pengoperasian - Halaman 8
Jelajahi secara online atau unduh pdf Panduan Instalasi dan Pengoperasian untuk Pengontrol Donaldson Torit Delta P Plus. Donaldson Torit Delta P Plus 16 halaman.
- 1. Table of Contents
- 2. Description
- 3. Operation
- 4. Inspection on Arrival
- 5. Electrical Wiring
- 6. Installation
- 7. Setpoint Adjustment
- 7. Quick Start Instructions
- 7. Adjustments
- 7. Password Protected Settings
- 8. Delta P Plus Control Calibration
- 9. Optional Settings
- 10. Troubleshooting
- 11. Replacement Parts
Donaldson Company, Inc.
Delta P Plus Control Calibration
The only user calibration is the zero adjustment of the
display. Due to slight changes in electronic components
over time or pressure within the plant environment, the
display may read something other than 0.0 while at rest.
Use the following procedure to recalibrate the operating
system.
1. Turn power to the Delta P Plus Control ON for a
minimum of 30-minutes to stabilize the operating
temperature.
2. Disconnect the pressure tubing, either leaving it to
atmosphere, or connecting the two barbed fittings
together with a short length of tubing.
3. Use the Menu key to select PAS.
indicates closed
alarm relay
menu
increase
setpoint
5
4. Press SET, then use the arrow keys to display "4",
press SET again.
5. Press the MENU key repeatedly until you reach P 14.
6. Press SET, then use the arrow keys to display "1",
press SET again.
7. After 10 seconds with no further button action, the
display will return to reading the pressure.
8. Connect one section of tubing from the control
enclosure's high-pressure port to the pressure tap on
the dirty-air plenum. Connect the remaining section
of tubing from the control enclosure's low-pressure
port to the pressure tap on the clean-air plenum.
Delta P Plus Control Display Panel
3-digit display
indicates closed
cleaning relay
set
downtime clean
decrease
setpoint