Configuration and commissioning

Configuration and commissioning of the device require
the use of the ETS
(Engineering Tool Software) program
®
V4 or later releases. These activities must be carried out
according to the design of the building automation sy-
stem done by a qualified planner. For the configuration
of the device parameters the corresponding application
program or the whole ekinex
loaded in the ETS program. For detailed information on
configuration options, refer to the application manual of
the device available on the website www.ekinex.com.
i
Important: After a download, it takes approxima-
tely 60 s for the sensor to stabilize before it enters
normal operation mode. During this settling period,
the sensor may not appear to react or perform its
programmed functions.
For the commissioning of the device the following activi-
ties are required:
• make the electrical connections as described above;
• turn on the bus power supply;
• switch the device operation to the programming mode
by pressing the programming pushbutton; the blue pro-
gramming LED (visible through the device lens) turns
ON;
• download into the device the physical address and the
configuration with the ETS
Warning! Do not mount on conductive surfa-
!
ce. Do not open the enclosure frequently. The
sensor is a low voltage circuit; never connect it
with the 230V line network. Do not run the KNX
wiring in the same conduit used by line network
wiring.
At the end of the download the operation of the device au-
tomatically returns to normal mode; during the program-
ming process, the programming LED is turned off. Now
the device is programmed and ready for use.
i
Note. The configuration and commissioning of KNX
devices require specialized skills. To acquire these
skills, you should attend the workshops at KNX cer-
tified training centers.
Reset of the device
The device can be reset from ETS
procedure:
• select the "Unload" - "Unload application and address"
option from the ETS
header;
®
• press the programming button on the device.
At the end of the operation the device is reset and brought
back to the factory conditions.
product database must be
®
program.
®
, with the following
®
!
Warning! The reset restores the device back to the
state of delivery from the factory. The address and
the value of the parameters set during configuration
will be lost.
Access to the slide switch
Using a screwdriver in the center groove (1), slightly pull
out the detector top cover (2). Rotate it up to access the
switch (3), then rotate it down and fix it in its original posi-
tion once the setting is complete.
1
Slide switch commands
• AUTO: by placing the switch in the central position, the
detector is in AUTO mode.
• ON: In ON mode, the load remains ON for 8 hours and
the LED flashes for 1 second every 5 seconds. After
8 hours, the detector automatically returns to AUTO
mode.
• OFF: in the OFF position, the load remains OFF for 8
hours and the LED flashes for 1 second every 5 secon-
ds. After 8 hours, the detector automatically returns to
AUTO mode.
In the event of a power failure, the detector enters AUTO
mode once the power is supplied again, even the switch
is set to ON or OFF.
Dimensions [mm]
5