DAB PUMPS ACTIVE DRIVER M/T 2.2 Instruksi Untuk Instalasi dan Pemeliharaan - Halaman 15
Jelajahi secara online atau unduh pdf Instruksi Untuk Instalasi dan Pemeliharaan untuk Unit Kontrol DAB PUMPS ACTIVE DRIVER M/T 2.2. DAB PUMPS ACTIVE DRIVER M/T 2.2 16 halaman.
14.
INDICATIONS ON THE DISPLAY
Identifying s.
Indications on the display in normal operation
Go
Electropump operating
Sb
Electropump waiting
User displays and settings (keys MODE & SET 2 seconds )
SP
Setting the set-point pressure ( in bar ). Default: 3 bar
Installer displays and settings
(keys MODE & SET & - 5 seconds )
rC
Setting the rated current of the electropump
rt
Setting the direction of rotation
od
Setting the operating mode
rP
Setting the pressure drop for restarting
Ad
Setting the interconnection address
Eb
Enabling the booster
Technical assistance displays and settings
(keys MODE & SET & + 5 seconds )
tb
Setting the reaction time of the water lack blockage
GP
Setting the gain of the proportional coefficient of the PI
GI
Setting the gain of the integral coefficient of the PI
FS
Setting the maximum rotation frequency of the electropump
dP
Setting the pressure differential at low flow rates
Ft
Setting the low flow rate threshold
CM
Exchange method
AE
Setting the enabling of anti-frost function
i 1
Setting the function of input 1 (float)
i 2
Setting the function of input 2 (set point selection)
i 3
Setting the function of input 3 (enable )
P1
Set point 1: input 2 function
Setting the function of output 1 (default value: 2; function: ON
O 1
alarm )
Setting the function of output 2 (default value: 2; function: ON
O 2
operating )
Displays of the main values (MODE key)
Fr
Display of the current rotation frequency (in Hz)
UP
Display of pressure (in bar)
C1
Display of the phase current of the electropump (in A)
Display of the version of the software with which the appliance is
UE
equipped
DISPLAY (keys SET & "-" for 2 seconds )
UF
Display of the flow
ZF
Display of zero flow
FM
Display of the maximum rotation frequency (in Hz)
tE
Display of the temperature of the power stages (in °C)
GS
Display of running status
FF
Display of fault history ( "+" e "-" to scroll )
Access to manual mode (keys SET & + & - 5 seconds ) (d)
MA
Operation in manual mode
System reset (keys MODE & SET & + & - )
"ZF"
General reset ( ZF appears when leaving reset and restarting )
Restoring the factory settings
(keys SET & + for 2 seconds when switching on)
EE
Saving and reading the factory settings on the EEprom
Error and status conditions
bL
Blockage due to water lack
LP
Blockage due to low supply voltage
HP
Blockage due to high supply voltage
LL
Low line voltage
ot
Blockage due to overheating of the power stages
oC
Blockage due to current overload in the electropump motor
oF
Blockage due to current overload in the output stages
Blockage due to direct short circuit between the phases of the
SC
output terminal
EC
Blockage due to incorrect setting of the rated current
E0...E7
Internal error 0...7
F1
Blockage due to input 1 status
F3
Blockage due to input 3 status
ENGLISH
Description
36
Factory parameters
A.D.
A.D.
A.D.
M/M 1.1
M/T 1.0
M/T 2.2
3.0 bar
3.0 bar
3.0 bar
0.0 A
0.0 A
00
00
01
01
01
0.3 bar
0.3 bar
0.3 bar
"- -"
"- -"
02
02
10 s
10 s
10 s
1.0
1.0
1.0
1.0
1.0
1.0
50
50
50
0.0 bar
0.0 bar
0.0 bar
15
15
15
01
01
01
01
01
01
01
01
2.5 bar
02
02
A.D.
A.D.
T/T 3.0
T/T 5.5
3.0 bar
3.0 bar
0.0 A
0.0 A
00
00
01
01
0.3 bar
0.3 bar
"- -"
"- -"
02
02
10 s
10 s
1.0
1.0
1.0
1.0
50
50
0.0 bar
0.0 bar
15
15
01
01
01
01
01
01
01
01
01
01
2.5 bar
2.5 bar
02
02
02
02