Test Procedure for Double Check Valve Assemblies
The following Test Procedure is one of several that is recog-
nized throughout the United States for verification of the
functioning of Backflow preventers and is not a specific
recommendation. The Ames test kit is capable of performing
any of the recognized Backflow test procedures.
TEST PROCEDURES
TESTING OF #1 CHECK VALVE
Step 1: Close #1 and #2 shut off valves.
Step 2: Open test cocks No. 2, 3, and 4. Verify that
No. 1 shut off valve is holding tight by observing that
the discharge of water from test cock No. 2 stops.
Step 3: Attach test kit "Vent" hose to No. 1 test cock;
"Low" hose to No. 2 test cock and "High" hose to No. 3
test cock. At this point valves (A) and (C) should be
open and (B) should be closed.
Step 4: Close test cock No. 4.
Step 5: Open test cock No.1. The needle of the
differential gauge will indicate a pressure in excess of
15 psi.
Step 6: Slowly open needle valve (B) until the differen-
tial gauge reads 10 psi. Then close (B). The gauge
reading will not change if No. 1 check is holding tight.
If No. 1 check is leaking, the gauge will drop to 0.
Requirements: The check valve shall be tight against
reverse flow under all pressure differentials.
Symptom
1. Check valve fails to hold
backpressure.
2. Chatter during flow
conditions
3. Low flows passing
through mainline
valve (3000 CIV only)
RP/IS-2000/3000CIV 0035
using Ames Test Kit
TESTING OF #2 CHECK VALVE
Step 1: Close test cock No. 1.
Step 2: Open test cock No. 4.
Step 3: Change "Low" hose from test cock No. 2 to
test cock No. 3. Change "High" hose from test cock
No. 3 to test cock No. 4. On the test kit, valves (A) and
(C) should be open and valve (B) should be closed.
Step 4: Open test cock No. 1. The pressure differential
gauge will indicate a pressure in excess of 15 psi.
Step 5: Slowly open needle valve (B) until the gauge
reads 10 psi, then close. If the gauge reading does not
change, No. 2 check valve is holding tight. If No. 2
check is leaking, the gauge will drop to 0.
Note in the above testing: Minor leakage in shut off
valve No. 2 will not affect the test results. However, in
the testing the No. 1 check, leaking shut off valve No. 1
would cause a good first check to fail the test.

TROUBLE SHOOTING GUIDE

Cause
a. Debris on check disc
sealing surface
b. Leaking gate valve
c. Damaged seat disc or
seat o-ring
d. Damaged guide holding
check open
e. Weak or broken spring
a. Worn, damaged or
defective guide
a. Mainline check fouled
b. Meter strainer plugged
c. Damaged mainline seat
disc or seat
d. Broken mainline spring
EDP# 1915232
C
A
B
Vent
Low
High
Solution
Disassemble and clean
Disassemble and clean or repair
Disassemble and replace
Disassemble clean or replace
Disassemble and replace spring
Disassemble and repair or
replace guide
Disassemble and clean
Disassemble and clean
Disassemble and replace
Disassemble and replace