GENERAL
S2000-IK Revision 03 Addressable Volumetric Passive Infrared (PIR) Motion Detector (hereinafter referred to as the
detector) is designed to be used indoors. It detects intrusion into protected areas and sends an alarm message to the
connected S2000-KDL controller via the two-wire multiplex addressable polling loop.
The S2000-IK rev.03 supports DPLS_v2.xx protocol.
The detector features:
A red LED to indicate detector's operability
Programming the address and communicating data with the connected S2000-KDL
A tamper switch to provide detection of unauthorized access as well as to adjust the detector
The detector is intended for round-the-clock operation.
SPECIFICATIONS
Input Voltage (via the polling loop of an S2000-KDL)
Current Consumption (via the loop of the S2000-KDL)
Pre-Operation Time
Detection Range
Target Speed
White Light Immunity
Sabotage-Resistant Zone
Operating Temperatures
Humidity
Overall Dimensions (H x W x D)
Weight
STANDARD DELIVERY
Find the following unpacking the S2000-IK rev.03:
S2000-IK rev.03 detector
This Instruction Manual
Two woodscrews 3.5×30
Two wall plugs 6×30
Two tapping screws 2.2×6.5
Bracket (to be ordered separately)
Package
MOUNTING LOCATION CONSIDERATIONS
The detector is intended to be used indoors. Considering a location to mount the detector, please take into account the
following:
1. Do not locate the detector above heaters, radiators, etc. or close to vent openings.
2. Do not locate the detector in places where it can be exposed to direct sun rays.
3. In capital facilities the detector should be mounted on a wall or in a corner.
4. Within light metal structures the detector should be mounted on structural frames (columns, trusses) rather than on
a wall or a corner.
5. To avoid condensation on the lens and case of the detector, do not attach the detector just over the entrance
opening.
6. There should not be any waving things like curtains and incandescent lamps in the detection area.
INSTRUCTION MANUAL
8 ÷ 10 VDC
0.65 mA max when indication is off
15 s max
0.3 m to 12 m
0.3 m/s to 3 m/s
Better than 6500 Lux
Yes
−30 to +50° C
Up to 95% at 25° C, non-condensing
68 mm × 93mm × 41 mm max
125 gram max