Akytec ITP11 Panduan Pengguna - Halaman 9
Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Alat Ukur Akytec ITP11. Akytec ITP11 16 halaman. Digital process display 4-20 ma
Juga untuk Akytec ITP11: Panduan Pengguna (15 halaman)
Installation and operation
5.3
Programming mode
In programming mode the necessary parameters can be changed (see Table 5.1).
To return to the operating mode, the
within 20 s, the device reverts to operating mode automatically.
The flowchart is presented in Fig. 4.
Table 5.1
Parameter
PS
di.P
di.Lo
di.Hi
td
Sqrt
Comments:
1. Factory settings are highlighted.
2. With particular setting parameters the device cannot display the necessary minus sign due to the re-
striction to four segments. The parameters are configured as follows:
di.Lo:
-999 è 4 mA
di.Hi:
9999 è 20 mA
With an input measured current of 3.8 mA the correct display should be "-1068". Due to the restriction to
four segments, the minus sign is removed and the display is "1068".
3. With particular setting parameters the device cannot actually display the necessary 5 figures due to the
restriction to four segments. The parameters are configured as follows:
di.Lo:
-999 è 4 mA
di.Hi:
9999 è 20 mA
With an input measured current of 20.8 mA the correct display should be "10548". Due to the restriction to
four segments, the first character is removed and the display is "0548".
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover· Germany · Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
button must be pressed for longer than 5 s. If no button is pressed
Comments
Password protection
Decimal point position
(from the right)
Lower limit (with 4 mA)
Upper limit (with 20 mA)
Filter time constant in seconds
Square root function on/off
Valid values
1)
on
oFF
– -– -– -–.
-– -– -–.-–
-– -–.-– -–
-–.-– -– -–
2)
-999...4.00...9999
3)
-999...20.00...9999
0...1...10
on
oFF
8