Electrex PLUS Panduan Memulai Cepat

Jelajahi secara online atau unduh pdf Panduan Memulai Cepat untuk Perangkat Perlindungan Electrex PLUS. Electrex PLUS 2 halaman.

The PLUS range of products are manufactured by Akse S.r.l. in compliance with
EMC 89/336/EEC regulations and in accordance with the following standards:
EMISSIONS = EN 50081-1 1992 EN5022 CLASS B, CISPR 22; IMMUNITY=
EN 50082-1 1992 (light industry) SAFETY=EN61010.
1
SAFETY
This instrument was manufactured and tested in compliance with class 2 IEC 1010 and VDE
411 standards, in accordance with group B VDE 0110 standards for operating voltages up to
250 VACrms phase to neutral. To maintain this condition and to ensure safe operation, the user
must comply with the indications and markings contained in the following instructions:
- when the instrument is received, before beginning installation, check that it is still intact and no
damage was incurred during the transport;
- before mounting, ensure that the operating voltage and mains voltage set are the same and then
proceed with the installation;
- the power supply does not require an earth connection;
- a 50 mA T fuse should be installed in the power supply circuit to the instrument;
- maintenance and/or repairs must be carried on only by qualified, authorized personnel;
- if there is ever the suspicion that safe use is no longer possible, the instrument must be discon-
nected and precautions must be taken against accidental use;
- operation is no longer safe when:
1) there are clearly visible damages;
2) the instrument no longer functions;
3) after a prolonged storage in unfavorable conditions;
4) after serious damages incurred during transport.
1.1
OPERATOR SAFETY
Read these pages carefully before installing and utilizing the instrument.
The instrument descibed in this user manual is intended for use by properly trained staff only.
Maintenance and/or repairs must be carried out by authorized personnel only. For proper, safe use
of the instrument and for maintenance and/or repair, it is essential that the persons instructed to
carry out these procedures follow normal safety precautions.
1.2
SYMBOLS
THIS SYMBOL MEANS: "READ THE INSTRUCTIONS"
2
POWER SUPPLY
The instrument must have a power supply with voltage ranging from 200÷240 VAC 50/60 Hz
using max. cable gauge 2.5 mm
and attached to the power supply terminals (see Fig. below).
2
The instrument power supply does not need an earth connection. The instrument requires the
installation of an external 50 m AT type fuse in the power supply circuit.
1 2 3 4
200 ÷ 240 VAC
2.1
CONNECTION OF THE VOLTAGE INPUT
Use cables with max. gauge 2,5 mm
and attach them to the screw terminals for voltage output.
2
The following drawings show how to connect the screw terminals to the phases. Refer to the
detailed wiring diagram to make the correct connection of the voltage input depending on the
selected instrument and on the plant it is installed into.
L1
L2
L3
N
Max 250 VAC
Phase-Neutral
1 2 3 4
Rev. 06/01
AKSE S.r.l. via Aldo Moro, 39 - 42100 Reggio Emilia (RE) - Italy - Tel. +39.0522.924244
ATTENTION:
5 6
8 9 10
50 mA T
PLUS
PLUS-P
PLUS-485
PLUS 4-20mA
PLUS-232
2.2
CONNECTION OF THE CURRENT INPUT
The instruments are equipped with terminals for connection of the current signal inputs. Connect
cables as indicated in the following diagrams.
The P1 and P2 indications identify the current correct direction.
N.B.: In case the CT connection is accidentally reversed, the instrument provides an
automatic compensation and, hence, inputs will be correct.
Above feature applies to reversed voltage connection too.
It is, however, absolutely essential to follow the sequence of the phases between voltage and
current.
N.B. The secondary CT must always short circuit when it is not connected to the instrument
to avoid damages and risks to the operator.
P1
P2
L1
P1
P2
L2
S1
S2
P1
P2
L3
S1
S2
N
S1
20 19 18 17
3
INSTRUMENT PROGRAMMING
The writing "WAIT" appears when the instrument is powered. After a few seconds the measure-
ment will be displayed (the LED on the key is lighted).
The programming key
is located at the bottom left corner of the front panel. To enter into
programming mode, press simultaneously the key
CT selection will appear:
Pressing the key
the available CT ratio is selected (see diagram in the following page)
Once the selection has been operated, press the programming key
Pressing simultaneously the key
and the key
simultaneously the key
and the key
The CT ratio prompted by default is 5/5.
Once the instrument has been programmed it is possible to disable the key
jumper placed near the current current inputs.
Once the jumper is removed it will not be possible to reset the counters and to change the CT ratio.
To enable again the programming functions, it is necessary to restore the jumper.
Remove the jumper for disabling set up and reset
3.1
ADDRESS OF THE INSTRUMENT (only for models 485/232)
After entering the programming page through
the address of the instrument will be displayed. The default address set by the manufacturer upon
delivery is:
It can be changed through: key
to select the digit
Key
to increase the digit
Key
to decrease the digit
The flashing digit is active.
To exit the programming, press key
a fourth time.
The maximum selectable number is 247.
English
S2
and the key
. On the display the
to confirm/exit set up.
the kWh values are zeroed.Pressing
the kVArh values are zeroed.
by removing the
12 11
11 12
and
, press the key
once more and
.
Fax. +39.0522.924245