Baumer Clever Level LBFH Panduan Petunjuk Pengoperasian - Halaman 8

Jelajahi secara online atau unduh pdf Panduan Petunjuk Pengoperasian untuk Aksesori Baumer Clever Level LBFH. Baumer Clever Level LBFH 34 halaman. Point level detection – hygienic/industrial

Baumer Clever Level LBFH Panduan Petunjuk Pengoperasian
CleverLevel
Point level detection – hygienic/industrial
7.
Configuration
The sensor can be configured either via qTeach,
remote teach or the FlexProgrammer. If formation
of foam or adhesion of media have to be detected,
a configuration with the FlexProgrammer will be
necessary.
Configuring with qTeach
A switch point can be configured via qTeach. When
doing so configuration must last 5 minutes at most,
otherwise the process will be canceled and will
have to be restarted.
9 Sensor is connected.
Briefly hold screwdriver or other metal object on
f
„
the qTeach detector.
The LED flashes magenta.
Dip sensor tip into medium.
f
„
Place screwdriver on qTeach detector again.
f
„
LED flashes green: Switch output SW1 is
defined and the sensor can differentiate between
air and medium.
LED flashes red: An error has occurred and the
configuration must be restarted. Changes have
not been saved.
In order to restart the configuration: Disconnect
f
„
sensor from voltage supply and connect it again.
To cancel the configuration: Place screwdriver
f
„
on qTeach detector for 5 seconds.
The LED will light up red and the configuration
can be restarted.
8 / 33
Level measurement
®
LBFH/I
Operating Instructions
Configuring via remote teach
Sensors that are built into places hard to access
can be configured via remote teach easily and
without any other help.
9 The remote teach function has been activated
with FlexProgrammer before the integration of
the sensor (see FlexProgrammer instructions).
Short-circuit switch output SW1 for more than
f
„
1 second with GND (0 V).
The LED flashes magenta.
Cover sensor tip with medium.
f
„
Short-circuit switch output SW1 again with
f
„
GND (0 V).
LED stops flashing.
Configuring with FlexProgrammer and PC
Switch points and damping of both switch outputs
can be set as desired with FlexProgrammer.
Connect FlexProgrammer to sensor.
f
„
Connect FlexProgrammer to PC and set
f
„
parameters (see FlexProgrammer instructions).
www.baumer.com