Baumer GNAMG. 153P Series Manual - Halaman 18

Jelajahi secara online atau unduh pdf Manual untuk Aksesori Baumer GNAMG. 153P Series. Baumer GNAMG. 153P Series 19 halaman. Inclination sensor with profibus-dp interface

Baumer GNAMG. 153P Series Manual
7.2.3.

Electrical connection of the inclination sensor

Release the cap nut of the cable gland.
Push the cap nut and seal insert with contact sleeve onto the cable sheath.
Strip the cable sheath and cores, shorten the shield film where it exists (see illustration)
Bend over the braided shield by approx. 90°.
Push the sealing insert with contact sleeve along as far as the braided shield. Insert the sealing insert
with contact sleeve and cable flush onto the cable gland and tighten the cap nut.
Clamps of the same designation are internally connected to each other.
For supply voltage use cable gland 3 only. For the bus lines, either optionally cable gland 1 or 2 may
be utilized. Observe the admissible core-cross-sections.
Guide the cores the shortest way from the cable gland to the terminal connector. Please observe the
admissible core-cross-sections, use ferrules in case of flexible cores.
Avoid any crossings of data lines and supply lines.
Seal up the unused cable gland using a sealing bolt (included in the delivery)
7.2.4.

View inside the inclination sensor

Baumer_GNAMG_Profibus_MA_EN
07.18
18/19
Baumer IVO GmbH & Co. KG
Villingen-Schwenningen, Germany