Hence the tracking mode is used, when the target is always visible for the sensor and cannot reliably be
selected with the Peak Selection Mode parameter.
When the track is lost, the sensor choses a new track and starts the same procedure again. For the time set
in Object Tracking Hold Time, the sensor tries to retrieve the track in the region the track got lost.
There are five given tracking modes:
Mode 0 Off (default)
o
No tracking is used
Mode 1
o
Medium (standard), should be used for slow moving objects less than 1 m/s
Mode 2
o
Slow, should be used for static or slow moving objects less than 0,01 m/s
Mode 3
o
Fast, should be used for fast moving objects up to 10 m/s
Mode 4
o
Predictive, can be use instead of the fast or standard mode
o
Calculates the predictive position of the object in the next step
o
Use with caution, can generate errors under certain circumstances

Object Tracking Hold Time

4.7.6
The parameter determines the time a track is held before it being discarded. For the time set in Object
Tracking Hold Time, the sensor tries to retrieve the track in the region the track got lost. The sensor output is
also retained for the time set.

4.8 Output Settings

Switching Output

4.8.1
The values from the selected internal output are directly set to the physical output layer.
Parameter name
DI/DO Settings.OUT1
Mode

Analog Output

4.8.2
4.8.2.1 Output Scale
Allows to change the values of the analog output range. For example: the default range is 4 to 20 mA, this
can be modified to e.g. 8 to 16mA. In terms of distance values mapped to analog values the modification
would mean that the default mapping of 4 mA = 700 mm and 20mA = 3000 mm, is modified to 8 mA =
700mm and 16mA = 3000 mm. The inverting of the analog output can be achieved by setting Analog Max to
a lower value as Analog .
When to use: When the master requires a different current range.
en_BA_RR30_IO-Link_V0.23.docx
13.01.2021/
Short Description
Select the SSC channel that is set on
the output Pin
28/40
Rights
Unit / Allowed values
rw
- SSC1 (default)
- SSC2
- SSC4