Baumer GXP8W Manual - Halaman 10

Jelajahi secara online atau unduh pdf Manual untuk Konverter Media Baumer GXP8W. Baumer GXP8W 13 halaman. Absolute encoder with devicenet

Baumer GXP8W Manual
Preset function
The preset function supports adjustment of the encoder zero point to the system's mechanical zero point.
The actual encoder position is set to the preset value. The internal offset value is calculated and stored in the
encoder. For storage into the non-volatile memory first the service "save" has to be carried out.
Attention: It is recommended to apply the preset function only in idle status of the encoder.
Chart: Diagnostic functions:
Attribute
Acces
Name
ID
s
80
read
Operating status
81
read
Singleturn-
resolution
82
read
Number of
revolutions
83
read
Alarm signals
84
read
Supported
alarm signals
85
read
Alarm-Flag
86
read
Warning signals
87
read
Supported
warning signals
88
read
Warn-Flag
89
read
Profile and
Software version
91
read
Offset
95
read
Encoder type
Manual_GXP8W_EN.doc
04.05.11
Data-
Significance
type
USINT
Encoder diagnosis
comprising the operating
status
UDINT
Internal resolution per
revolutions
UINT
Internal number of
revolutions
UINT
Malfunction may lead to
wrong encoder position
UINT
Information on the alarm
signals supported
BOOL
Indicates occuring alarm
signal (depending on
attribute 83.)
UINT
internal parameters
beyond tolerances
UINT
Information on the
warning signals supported
BOOL
Indicates occuring
warning signal
(depending on attribute
86)
UDINT
Low-Word: Profile
High-Word: Software-
Version
DINT
The offset is calculated
within the preset function
and will shift the position
value by the calculated
value
UINT
Describing the encoder
type
10/13
Values
Bit 0
0 = sense of rotation CW
1 = sense of rotation CCW
Bit 1
0 = diagnosis not supported
1 = diagnosis supported
Bit 2
0 = scaling OFF
1 = scaling ON
see operating parameters
see operating parameters
Bit 0
0 = no position error
1 = position error
Bit 0
0 = position error not
supported
1 = position error supported
0 = OK
1 = Alarm
Bit 4
Lithium cell voltage
0 = OK
1 = too low
Bit 4
Alarm signal lithium cell
voltage
0 = not supported
1 = supported
0 = OK
1 = warning signal
Baumer IVO GmbH & Co. KG
Villingen-Schwenningen, Germany