1.1.7 Key Switches
The key switches are used to enable access to the system and to configure the system to operating modes.
Switch

Operation

2-Position: Enables user controls and Level-2 access – key is
ACCESS
trapped in the enable position.
(Controls)
MODE
3-Position: Enables test and engineer modes in addition to
the normal "Operate" mode.
(Engineer)
2 OPERATION
The basic operation of the panel is automatic. The panel will send messages to the pagers in the event of a fire
alarm when it receives the signal from the connected fire alarm control panel.
2.1 Manual Messages
It is possible to manually send messages to all or to specific pagers by using the message buttons (if these
buttons have been configured).
If required, insert and turn the "Access Enable" key.
Press the required Message Button.
The pre-programmed message will be sent and the blue transmit indicator will illuminate during the
transmission.
2.2 Fault Conditions
If the system develops a fault, this is indicated on the display and on the LED indicators.
[System Status]
1 of
1 conditions:
INPUT 8
OPEN CIRCUIT
LAST MESSAGE SENT...
FAULT >INPUT 8 >OPEN
The first fault condition is shown along with the number of fault conditions present.
If there is more than one fault condition present, use the  buttons to scroll through the list of fault conditions.
If there is more text in the last message sent than can fit on the display, use the  buttons to scroll through
the remainder of the text message.
Make a note of the fault conditions and contact your service / maintenance company.
2.3 Power Failure
If the main power fails, the panel will fully operate using its internal battery. The Power LED will flash and the
display backlight will be turned off or dimmed to save energy.
Pressing a number button or navigation button will turn the backlight back on again for five minutes.