Baumer ISI Series Panduan Petunjuk Pengoperasian - Halaman 10
Jelajahi secara online atau unduh pdf Panduan Petunjuk Pengoperasian untuk Penghitung Uang Tunai Baumer ISI Series. Baumer ISI Series 20 halaman. Display counter
ISI30, ISI31, ISI32, ISI33
Screw terminal 3:
Reset input, active for negative edge Contact input / Open
Collector NPN (switching at 0 V DC)
Low level:
0 ... 0,7 V DC
High level:
3 ... 30 V DC
Min. pulse duration:
50 ms
Input resistance:
approximately 2,2 MOhm
Screw terminal 5:
Operating mode switch (Mode) Contact input / Open Collector
NPN (switching at 0 V DC)
Low level:
0 ... 0,7 V DC
High level:
3 ... 5 V DC
Input resistance:
approximately 2,2 MOhm
Function:
see Table 2
Input specification and pin assignment (AC-version)
Screw terminal
No. 1
Designation
Model
ISI30.013AX01
counting
ISI31.013AX01
subtracting
counting
ISI32.013AX01
direction
Table 3
Screw terminals 1 and 3:
Function:
see Table 3
Optocoupler input 10 ... 260 V AC/V DC
galvanic isolation, active for high signal
Min. pulse duration: 16 ms
Max frequency:
approximately 30 Hz
Low level:
0 ... 2 V AC/V DC
High level:
10 ... 260 V AC/V DC
Input resistance:
approximately 160 kOhm
Screw terminal 2:
Common AC/DC, common connection for the optocoupler inputs
(screw terminals 1 and 3).
Screw terminal 4:
Electrical locking of the reset key Contact input / Open
Collector NPN (switching at 0 V DC)
Low level:
0 ... 0,7 V DC
High level:
3 ... 5 V DC
Input resistance:
approximately 2,2 MOhm
Input not active:
Reset key locked
Input in contact with GND:
Reset key unlocked
10
No. 3
No. 2
INP A
Common
INP B AC/DC
AC/DC
AC/DC
reset
adding
counting
Screw terminal 4:
Electrical locking of the reset key Contact input / Open Collector
NPN (switching at 0 V DC)
Low level:
High level:
Input resistance:
Input not active:
Input in contact
with GND:
Screw terminal 6:
GND connection common for all inputs
Screw terminal 7:
(–) external power supply for the LCD backlight option
Screw terminal 8:
(+) external power supply for the LCD backlight option
(24 V DC ±20%, 50 mA)
No. 4
Reset Enable
NPN reset key lok-
king input, Contact
with GND. key free.
Screw terminal 5:
Function: see table 3, active for negative edge Contact input
/ Open Collector NPN (switching at 0 V DC)
Low level:
High level:
Min. pulse duration:
Input resistance:
Input high:
Input low :
Screw terminal 6:
Common GND connection for screw terminal 4 (reset key
locking input) and screw terminal 5 (reset input).
Screw terminal 7:
(–) external power supply for the backlight option
Screw terminal 8:
(+) external power supply for the backlight option
(24 V ±20%, 50 mA)
www.b umer.com
0 ... 0,7 V DC
3 ... 5 V DC
approximately. 2,2 MOhm
Reset key locked
Reset key unlocked
No 5
No. 6
Reset
GND
not connected
NPN reset input
0 ... 0,7 V DC
3 ... 5 V DC
50 ms
approximately 2,2 MOhm
- - -
Reset of the counter
Dynamic resetting behaviour
No. 7 No. 8
BL
BL
–
+