Adding operating mode
External reset with continuous signal
Reset
Preset
Start count
value
Output
Automatic reset with pulse signal
Reset
Preset
Start count
value
Output
External reset with pulse signal
Reset
Preset
Start count
value
Output
Tw
Counter overrun in minus The minus counting range is 0 to -9999. If -9999 is exceeded, the
Counter overrun in plus The plus counting range is 0 to 199999. If 100000 is exceeded, prefix
5.2
Output responses (output modes)
Signal output response is determined by the following:
- Operating mode selected on DIP-switch 1
- Reset mode selected on DIP-switch 2
- Programming of the preset value, start count value, output time,
output signal logic and output signal function;
- External resetting;
- External counting direction control.
The diagrams below show the output signal responses.
Tw
5.3
Counter overrun response
range counter is automatically reset to zero.
range zero suppression is cut out and the LED X flashes, indicating the
overrun. If 199999 is exceeded, the counter is automatically reset to
100000.
www.baumer.com
Subtracting operating mode
Reset
Preset
Start count
value
Output
Reset
Preset
Start count
value
Output
Reset
Preset
Start count
value
Output
Tw
NE210
Tw
39