4.2.6. Set actual value as preset „Z" (5Ah)
Command "Z" is utilized to set the actual value at any optional value. The required position value is transmitted
to SPA. The SPA will calculate a so-called "preset offset" value relating to the true absolute encoder position.
When calculating the preset offset, any programmed offset transmitted by command "U" will be considered, so
that after having accomplished command "Z" the current value always equals the preset.
Note: When altering the resolution (see command „a") from 1/100 to 1/10 or vice-versa, any already assigned
preset must be assigned anew. The internally calculated offset is available in the resolution previously
programmed.
The indicated actual value is composed as follows:
actual value
Actual value
indicated actual value for readout by interface
Anz
Actual value
internal absolute actual value.
Abs
Preset offset
offset generated by command „Z".
Offset
supplementary offset defined by command „U". This function however must be enabled in
command bit parameter ‚a' (61h), otherwise applies offset = 0.
Example 1: Readout presently active preset
SOH Adr Cmd EOT CRC
Transmission
01h
20h
SOH Adr Cmd
Response
01h
20h
Example 2: Set actual value as preset value (preset = 17.25)
SOH Adr Cmd
Transmission
01h
20h
SOH Adr Cmd
Response
01h
20h
Example 3: Set actual value as preset in all SPAs by broadcast command
SOH Adr Cmd
Transmission
01h
83h
Response
not confirmed
4.2.7. Indicate optional column of figures in upper line „t" (74h)
This command is utilized to indicate a 5-digit number in the upper line of the display. The numerical column is
indicated less dot respectively comma. Preceding zeroes as well as both arrows are suppressed. The bottom
line still indicates the actual value.
The numerals are indicated in the display until any command except „t", „u" or „R" is received by interface. The
number will be retained after power failure.
Example: (column of figures = 054321)
SOH
Adr
Transmission
01h
20h
SOH
Adr
Response
01h
20h
= actual value
Anz
5Ah
04h
38h
preset = 2.50
5Ah
30h
30h
30h
32h
preset = 17.25
5Ah
30h
30h
31h
37h
preset = 17.25
5Ah
30h
30h
31h
37h
preset = 17.25
5Ah
30h
30h
31h
37h
Cmd
Column of figures = 054321
74h
30h
35h
34h
Cmd
Column of figures = 054321
74h
30h
35h
34h
www.baumer.com
+ preset offset + offset
Abs
EOT CRC
35h
30h
04h
27h
EOT CRC
04h
09h
32h
35h
EOT CRC
32h
35h
04h
09h
EOT CRC
32h
35h
04h
AAh
EOT
33h
32h
31h
04h
EOT
04h
33h
32h
31h
CRC
C6h
CRC
C6h
N 150