INSTRUCTION & SERVICE MANUAL
AL105
Category W-x-y (Wall mounted):
Wall mounted, where x is the maximum
mounting height from the floor and y is the
maximum length of the sides of the square
floor area covered by the VAD.
• All models are approved for use as Audible Signal and Visual Appliance
for use as General Signaling: UL464A & CSA C22.2 No 205-17
• Type 4 / 4X / 3R / 13, IP66 independently tested to EN60529:1991
• -40°C to +66°C / -40°C to +151°F
General Signaling Canada:
AL105.xxx.2 DC: -40°C to +55°C / -40°F to +131°F
AL105.xxx.7 AC: -40°C to +40°C / -40°F to +104°F
• To maintain Ingress Protection, cable entries must be fitted with suitably rated cable glands or stopping plugs
• Mounting - Units can be mounted using 2 of the 4-off ø7mm holes in the mounting lugs or through the back of the housing using the
supplied gasket.
• EOL Monitoring (DC Only): End of Line Devices may be fitted between the +ve & -ve terminals of the PCBA. Please ensure that the device
legs meet the wire size range stated for the connection terminals and are fitted correctly in order to avoid a short. Refer to the compatible
control panel specification for EOL device values and ratings
Nominal
Model
Voltage
AL105.012.2
12V dc
AL105.024.2
24V dc
AL105.048.2
48V dc
AL105.024.7
24V ac
AL105.048.7
48V ac
AL105.115.7
115 Vac
AL105.230.7
230 Vac
*Nominal Voltage, 1Hz Flash Pattern & Tone 12; #Worst-case input voltage and worst case flash pattern
Attention: Installation must be carried out by an electrician in compliance with the National Electrical Code, NFPA 70 or CSA 22.1 Canadian Electrical
Code, Part I, Safety Standard for Electrical Installations, Section 32. / L'installation doit exclusivement être réalisée par du personnel qualifié, conformé
ment au code national d'électricité américain, NFPA 70 ou CSA 22.1 Code canadien de l'électricité, première partie, norme de sécurité relative aux
installations électriques, Section 32
AL105.024.2 & AL105.48 .2 LIGHT OUTPUT
y
Nominal Operating Current*
Voltage Range
Beacon
11.5-14Vdc
20-28Vdc
42-52Vdc
24-28Vac 50/60Hz
42-54Vac 50/60Hz
103.5-126.5Vac
50/60Hz
207-253Vac
50/60Hz
Note: CPR aproved units must be
positioned sounder on top,
x
Coverage Area According to EN54-23
(Only units in the following
table are VdS Approved)
y
Unit
Approved Beacon for EN54-23 Applications:
Clear lenses are compliant with EN54-23
Sounder
341mA
17mA
250mA
33.5mA
170mA
113mA
300mA
42.5mA
250mA
42mA
70mA
25mA
35mA
17mA
beacon below.
Power
Category W
W-2.4-4.8
11W
V=55.3m ³
W-2.5-5
14W
V=62.5m ³
#
Max Operating RMS
Beacon
531mA
271mA
170mA
426mA
360mA
101mA
58mA
Sounder
125mA
42.5mA