WARNING! Failure to disconnect power prior to connecting nrgSMART PDUs will damage the nrgCONTROL-BT.
Power should be removed prior to connecting panels and servicing.
1. Remove the nrgNET connectors from the nrgNET OUT 1 and nrgNET OUT 2 on the rear of the nrgCONTROL-BT.
2. Insert the two service links provided into the nrgNET OUT 1 and nrgNET OUT 2 on the rear of the nrgCONTROL-BT
as shown in Fig. 7. Service links should be secured to the tie bar using the tie wraps provided. Insert the tie wrap
through the slots in the tie bar on each side of the service link and tighten to secure in place.
3. For nrgNET wiring — wiring used to daisy chain the nrgCONTROL-BT panel to the attached nrgSMART panels
(PDUs) — do the following:
3
a. Strip
/
-inch of insulation away from the four conductor wires in the nrgNET cable.
8
b. Insert the wires into the connector and tighten the screws to hold the wires in place making sure to
connect the proper wire to the pins as illustrated in nrgNET pin outs table and in Fig. 7.
c. Insert the connector into the open end of the service link on the rear of the nrgCONTROL-BT.
4. nrgNET cables can be dressed to the tie bar using the tie wraps provided.
WARNING! Failure to connect the wires to the proper pins can result in a failure to communicate between the
nrgCONTROL-BT and the attached nrgSMART panels.
nrgNET Pin Outs
Pin Number
Label
Pin 1
COM +
Pin 2
COM -
Pin 3
SHLD
Pin 4
PWR +
Pin 5
PWR -
nrgCONTROL-BT
Wire Color
White
Blue
Drain wire
Black
Red

Fig. 7: nrgNET connections

All rights reserved. 07.20.2018 145122-4
8