Dover HYDRO HYDSPD0093M Panduan Pengguna - Halaman 11
Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Pengontrol Dover HYDRO HYDSPD0093M. Dover HYDRO HYDSPD0093M 20 halaman. With evoclean
3.OO programming (continued)
3.O4 Product Parameters
1) Click on Products in the left-hand column, the below page will open.
2) Product – choose the valve number you want to program i.e. 1. Remember the product order starts with the valve next to
the water one.
3) Name – enter the name of the product.
4) Properties:
•
Specific Gravity – enter the specific gravity of the product. This can be obtained from your chemist.
•
Concentration – enter the concentration of the product. (Always 100% unless the product is a stock solution or the
dosages are referred to the raw material only).
•
K/F (mls/pulse or oz/pulse) –performing calibration will set this.
•
Flow rate (L or oz per minute) – performing calibration will set this.
5) Dosage:
•
Priority - this must be set for each chemical, if "0" the chemical will not dispense.
•
Priority must be set higher for the products in the shortest stage of the wash program e.g.
•
Softener should be set at 1-2.
•
Priority determines the next machine in the queue to receive the dosage depending on the product it is asking for.
•
Mode - time or flow meter. Time is the recommended mode for the Multi-Washer 3000 with EvoClean.
•
Estate - Liquid or stock solution. For the Multi-Washer 3000 this will always be liquid.
6) Alarms:
•
Skipped alarms – start up at 1 and then change to 3 once start-up has been completed, this is the amount of times the
unit can receive an error before it alarms. If an error is received and then the next dosage is correct the skipped alarm
will default back to 0.
•
Level contact - This suction lance setting can be set to normally open or normally closed, but all Hydro Systems'
lances use normally open.
7) Click on Save at the bottom of the page.
Product Parameters
11