COMBAT HVE 450 Panduan Pemasangan, Pengoperasian, dan Servis - Halaman 9

Jelajahi secara online atau unduh pdf Panduan Pemasangan, Pengoperasian, dan Servis untuk Kipas angin COMBAT HVE 450. COMBAT HVE 450 12 halaman. Energy saving fans with control options

COMBAT HVE 450 Panduan Pemasangan, Pengoperasian, dan Servis
Section 6
Troubleshooting

6.1 Sequence of Operation

DANGER
The WAC6 Fan Control offers manual control over HVE
fan speeds. See Page 8, Section 5 wiring diagrams to
utilize the HVE Fan thermostat.
In this case, each fan will turn on when the temperature
at the fan exceeds the thermostat set point. The fans
speed will be determined by the speed set on the
Electrical Shock Hazard
controller.
Disconnect electrics before service
To disable the HVE fan thermostat, wire line power
Equipment must be properly grounded.
to terminal
"1" rather than terminal
"L" . In this
Failure to follow these instructions can result
configuration, the fan control ON/OFF switch will be
in death or electrical shock
used to turn HVE fan(s) on and off.
If a fan control is not used, the built in thermostat
on each HVE fan will turn equipment on when the
temperature at the fan exceeds the set point of the
thermostat.
9