Condenser specification
W1 Width
D1 Depth
H1 Height
Electrical
Maximum circuit
Minimum circuit ampacity
Air temperature
Maximum refrigerant line
run length
Maximum line rise above
evaporator
Evaporator mounting above
condenser
Evaporator mounting maximum
refrigeration line drop
Cooling capacity for ice machines
connected to ride systems
Rack systems (EPR valve to be
supplied by installer)
Ice production
Approximate ship weight
NOTE: For outdoor use only
1. Condensing units have a liquid suction line heat exchanger. The entire
liquid line should be insulated separately from the suction line.
2. Outdoor installation of low side is not recommended and will void
warranty.
Remote 700 series ice machine
36.25" (92.1 cm)
25.50" (64.8 cm)
26.10" (66.3 cm)
208-230 V, 60 Hz
HVACR break size 15 A
10.7 A
-20 - 120 F (29 - 49 C)
100' (30.5 m)
35' (10.7 m)
15' (4.6 m)
15' (4.6 m)
5200 BTU/hr
set to 0 F (-18 C)
see ice production charts on page 8
225 lb (102.0 kg)
Condenser dimensional drawing
D1
W1
H1