3 Card Configuration Setup
Adding a Card to the Design
Expand the Panel (in the "Site List") and select the "Peripheral Bus" node; this will bring up a list of available
cards that can be connected to the peripheral bus in the "Device Selector".
Select the 10 Way Input Monitor and add it to the design.
The device must be added to the same DIP Switch address as the one set on the card.
Configuring Inputs
Input configuration is performed along the same line as configuring any other input device.
Setting the "Input Action" to "No Action" has the following impact:
-
Input is disabled at the hardware end (overall power consumption is reduced)
-
End of Line resistors are not required for unused inputs.
By default all inputs are set to Un-Monitored; "Input Monitored" should be checked for any input that needs to
detect Open circuit and Short circuit faults.
8
www.advancedco.com