Amprobe ACD-41PQ Panduan Pengguna - Halaman 19

Jelajahi secara online atau unduh pdf Panduan Pengguna untuk Alat Ukur Amprobe ACD-41PQ. Amprobe ACD-41PQ 19 halaman. 1000a clamp-on power meters

Power
RANGE
0 ~ 600.0kVA
@ PF = 0.99 ~ 0.1
RANGE
0 ~ 600.0kW / kVAR
@ PF = 0.99 ~ 0.70
@ PF = 0.70 ~ 0.50
@ PF = 0.50 ~ 0.30
@ PF = 0.30 ~ 0.20
Specified accuracy is for ACA clamp measurement at the center of jaws. When the
1)
conductor is not positioned at the jaw center, position errors introduced are:
Add 1% to specified accuracy for ACA measurements made WITHIN jaw marking
lines (away from jaw opening)
Accuracy is not specified for ACA measurement made BEYOND jaw marking lines
(toward jaws opening)
Add 1% to specified accuracy @ ACA fundamental < 5A or ACV fundamental < 90V.
2)
Accuracy is not specified @ ACA fundamental < 1A or ACV fundamental < 30V
Add 1% to specified accuracy @ ACA fundamental < 5A or ACV fundamental < 90V.
3)
Accuracy is not specified @ ACA fundamental < 2A or ACV fundamental < 50V
A-lags
Indication:
1)
"A-lags" LCD annunciator turns on to indicate an inductive circuit, or Current A lags
Voltage V (i.e., phase-shift angle θ is "+").
A-lags Indication is specified at 50/60Hz fundamental without harmonics, and at ACV >
1)
90V, ACA > 9A, & PF < 0.95
F ~ 10th
2.0%+6d
F ~ 10th
11th ~ 25th
2.0%+6d
3.5%+6d
3.0%+6d
4.5%+6d
10%+6d
Accuracy
1) 2)
11th ~ 46th
3.5%+6d
Accuracy
1) 3)
26th ~ 46th
4.5%+6d
18
47th ~ 51st
5.5%+6d
47th ~ 51st
10%+6d
15%+6d