AirStage AGYA004GCAH Panduan Instalasi - Halaman 11
Jelajahi secara online atau unduh pdf Panduan Instalasi untuk Pendingin Udara AirStage AGYA004GCAH. AirStage AGYA004GCAH 15 halaman. Indoor unit (floor type)
Juga untuk AirStage AGYA004GCAH: Panduan Pengoperasian (8 halaman)
7.3. Custom code setting
• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
• Perform the setting for both the indoor unit and the remote controller.
Confusion
Indoor unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to the figure and table below.
DIP switch
"SET3"
DIP switch
7.4. Function setting
Please make this setting after completing all construction works.
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "7.2. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Setting num-
Function
number
ber
00 Standard
Filter
indicator
11
01 Longer
interval
02 Shorter
00 Enable
01 Disable
Filter
Display
indicator
13
only on
action
02
central
remote
controller
00 Standard
Vertical
airflow
23
direction
01 Adjust
00 Standard
Horizontal
swing
24
01 Left half
airflow
direction
02 Right half
00 Standard
Cool air
tempera-
30
01 Adjust (1)
ture trigger
02 Adjust (2)
00 Standard
Heat air
01 Adjust (1)
tempera-
31
02 Adjust (2)
ture trigger
03 Adjust (3)
Code change
A
B
C
A
B
C
OFF
ON
SW 1
DIP switch
SW 2
"SET3"
SW 3
SW 4
Custom code
A (Factory
SET3
B
C
setting)
SW1
OFF
ON
OFF
SW2
OFF
OFF
ON
WARNING
Default
Details
○
Adjust the filter cleaning interval noti-
fication. If the notification is too early,
change to setting 01. If the notifica-
tion is too late, change to setting 02.
○
Enable or disable the filter indicator.
Setting 02 is for use with a central
remote controller.
Adjust the vertical airflow direction.
○
Adjust the horizontal swing airflow
○
direction.
(For horizontal swing equipped
models)
○
Adjust the cool air trigger tempera-
ture. To lower the trigger temperature,
use setting 01. To raise the trigger
temperature, use setting 02.
Adjust the heat air trigger
○
temperature. To lower the trigger tem-
perature by 6 degrees C, use setting
01. To lower the trigger temperature
by 4 degrees C, use setting 02. To
raise the trigger temperature, use
setting 03.
Auto restart
40
D
D
Cool Air
43
Prevention
External
46
control
D
ON
ON
Error report
47
target
Fan setting
when
cooling
49
thermostat
OFF
(Forbidden)
60
(Forbidden)
61
(Forbidden)
62
Auto mode
68
type
Deadband
69
value
Enable or disable automatic system
00 Enable
restart after a power outage.
* Auto restart is an emergency func-
tion such as for power failure etc.
Do not start and stop the indoor unit
○
by this function in normal operation.
01 Disable
Be sure to operate by the control
unit, converter or external input
device.
Restrain the cold airflow with making
○
00 Super low
the airflow lower when starting heat-
ing operation. To correspond to the
ventilation, set to 01.
Follow the
setting
○
01
on the
remote
controller
Allow an external controller to start
○
or stop the system, or to perform an
00 Start/Stop
emergency stop.
* If an emergency stop is performed
from an external controller, all re-
Emergen-
frigerant systems will be disabled.
01
cy stop
* If forced stop is set, indoor unit
stops by the input to the external
Forced
input terminals, and Start/Stop by a
02
Stop
remote controller is restricted.
○
Change the target for reporting er-
00 All
rors. Errors can either be reported in
Display
all locations, or only on the central
only on
remote controller.
01
central
remote
controller
Follow the
When set to 01, the fan stops when
setting
the thermostat is OFF in cooling
○
00
on the
operation. Connection of the wired re-
remote
mote controller (2-wire type or 3-wire
controller
type) and switching its thermistor are
necessary.
01 Stop
○
00
○
00
○
00
Single
setpoint
Switch the setting method of
auto
○
00
auto mode to single or dual
mode
(cooling/heating).
(tradi-
For heat pump systems, it is
tional)
necessary to set the master indoor
Dual set-
unit (by wired remote controller).
point auto
01
mode
○
00 0°C
01 0.5°C
02 1.0°C
03 1.5°C
Choose the minimum temperature
04 2.0°C
between cooling and heating
settings (deadband) for Dual
05 2.5°C
setpoint auto mode (set in No. 68).
06 3.0°C
07 3.5°C
08 4.0°C
09 4.5°C
En-10