AirStage ARUL18RLAV Panduan Instalasi
For U.S.A. and Canada :
When installing this system in high humidity locations, install using ground fault
equipment breakers (often referred to in other countries as an ELCB earth leakage
current breaker) to reduce the risk of leaking current which result in electric shock or
potential fi re.
For others:
Install an earth (ground) leakage breaker. In addition, install the earth (ground) leakage
breaker so that the entire AC main power supply is cut off at the same time. Otherwise,
electric shock or fi re could result.
Always connect the earth (ground) cable.
Improper earthing (grounding) work can cause electric shocks.
Install the remote controller cables so as not to be direct touched with your hand.
Perform wiring work in accordance with standards so that the air conditioner can be
operated safely and positively.
Connect the connection cable fi rmly to the terminal board. Imperfect installation may
cause a fi re.
If the supply cord is damaged, it must be replaced by the manufacturer, its service
agent or similarly qualifi ed persons in order to avoid a hazard.
Earth (Ground) the unit.
Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a
telephone earth (ground) cable.
Improper earthing (grounding) may cause electric shock.
Do not connect power supply cables to the transmission or remote controller terminals,
as this will damage the product.
Never bundle the power supply cable and transmission cable, remote controller cable
together.
Separate these cable by 1-31/32 in. (50 mm) or more.
Bundling these cables together will cause miss operation or breakdown.
When handling PCB, static electricity charged in the body may cause malfunction of
the PCB. Follow the cautions below:
• Establish an earth (ground) for the indoor and outdoor units and peripheral devices.
• Cut power (breaker) off.
• Touch metal part of the indoor and outdoor units for more than 10 seconds to
discharge static electricity charged in the body.
• Do not touch terminals of parts and patterns implemented on PCB.

6.1. Electrical requirement

Voltage rating
Operating range
• Select the power cable type and size in accordance with relevant local and national
regulations.
• Specifi cations for local wiring power cord and branch wiring are in compliance with local code.
• Select the correct cable type and size according to the country or region's regulations.
• Max. wire length: Set a length so that the voltage drop is less than 2%. Increase the wire
diameter when the wire length is long.
Refer to the table for the breaker specifi cations of each installation condition.
Perform the power crossover wiring within the range of the same refrigerant system.When the crossover
wiring is done, make a connection for indoor unit to satisfy conditions A and B below.
A. Current breaker requirements
Model
ARUL7RLAV
ARUL9RLAV
ARUL12RLAV
ARUL14RLAV
ARUL18RLAV
MCA: Minimum Circuit Ampacity
MOP: Maximum Overcurrent Protection
When the power crossover wiring is done, make it so that the total of the MCA of the
connected indoor equipment does not exceed the 15 A.
En-11
WARNING
CAUTION
208/ 230 V
187 to 253 V
MCA
MOP (Fuse capacity)
0.38 A
0.42 A
0.46 A
20 A
0.74 A
0.66 A
B. Earth leakage breaker requirements
Breaker capacity
30 mA, 0.1 sec or less
100 mA, 0.1 sec or less
200 mA, 0.1 sec or less
If the number of units of connected indoor unit exceeds the upper limit, either add breakers
or use a breaker with large capacitance.
6.1.1 Transmission and remote controller wiring specifi cations
Follow the specifi cations below for the transmission and remote controller cable.
Cable size
Transmission
22 AWG
cable
(0.33 mm²)
Remote
22 AWG
controller cable
(0.33 mm²)

6.2. Wiring method

(EXAMPLE)
Power supply
Breaker 1
Breaker 2
Outdoor unit
Transmission
Power supply
Indoor unit
Transmission
Power
Power
supply
supply
Remote
control
Breaker 2
Breaker 2
Breaker 1
Breaker 1
Remote
controller
(Master)
Power supply
Power supply
(Crossover wiring of power supply)
Indoor unit
Power
supply
Remote
control
Pull box
Breaker 2
Breaker 1
Remote
controller
(Master)
Power supply
Maximum connectable indoor unit
8
27
39 (Upper limit of the refrigerant system)
Wire type
Remarks
LEVEL 4
(NEMA)
non-polar
LONWORKS ®
2core, twisted
compatible cable
pair solid core
diameter 1/32 in.
(0.65mm)
Sheathed PVC
Polar 3 core Twisted pair
cable
Breaker 1 : Earth leakage breaker
(GFCI breaker)
Breaker 2 : C u r r e n t
b r e a k e r
(MOP breaker)
Indoor unit
Transmission
Transmission
Power
supply
Remote
control
Breaker 2
Breaker 1
Remote
controller
(Slave)
Power supply
Indoor unit
Power
Power
supply
supply
Remote
control
Pull box
Remote
controller
(Slave)
Indoor unit
Remote
control
Remote
controller
Indoor unit
Remote
control
Remote
controller