5. Initial start-up
WARNING! Before start-up, the user has to check for
proper installation and for any visible defects.
WARNING! The device can be started and operated by
authorized personnel only, who have read and under-
stood the operating manual!
WARNING! The device has to be used within the
technical specifications, only (compare the data in the
data sheet)!
6. Operation
Set point adjustment – factory set
The set points are factory set either to ordered values or to
BD SENSORS standard:
Switching function
Switching mode
Switch on point
Switch off point
Switch on/switch off delay
Set point adjustment – user specific
Every DS 6 can be quickly and comfortably configured either
by means of the optionally available configuration kits
CIS 685 or CIS 686 as well as the programming device P6.
These devices can be ordered as accessories from
BD SENSORS. In the following, a short description of these
possibilities is given:
Configuration via configuration kit
The DS 6 can be connected to a PC via the programming
adapter and configured by the programming-software P-Set.
The setting of the following parameters for both set points is
possible:
- operation mode (hysteresis or window mode)
- switch-on and switch-off point
- set point negation
- switch on and switch off delay
The programming adapter is part of the programming kits
CIS 685 and CIS 686 which contains i.a. a CD-ROM with the
configuration software P-Set. All cables required for connect-
ing the pressure switch have to be plugged to the program-
ming adapter (included in scope of delivery). The user only
®
requires a Windows
PC with serial interface (CIS 685) or
USB-interface (CIS 686). Installing the configuration soft-
ware P-Set is very easy. P-Set runs on all Windows
(95, 98, ME, 2000, NT, XP).
Fig. 3 Programming
Fig. 2 Programming
adapter
Software
Configuration via programming device P6
The programming device P6 is simply plugged between
DS 6 and the female connector. Via two push-buttons and a
4-digit LED display, all possible settings can be realized. The
menu system of the device includes 27 menus and is easy
to handle. The following menus are – among others –
available for configuration:
- read all and store all
- operation mode
- switch-on and switch-off point
- set point negation
- switch on and switch off delay
- teach switch-on and switch-off point
- load of stored configurations
- storage off current configurations
- showing the current pressure value
- showing the limits of the measuring range
Fig. 4 Programming device P 6
7. Placing out of service
WARNING! When dismantling the device, it must
always be done in the depressurized and currentless
condition! Check also if the medium has to be drained
off before dismantling!
WARNING! Depending on the medium, it may cause
danger for the user. Comply therefore with adequate
precautions for purification.
8. Maintenance
In principle, this device is maintenance-free. If desired, the
housing of the device can be cleaned when switched of
using a damp cloth and non-aggressive cleaning solutions.
Depending on the measuring medium, however, the dia-
phragm may be polluted or coated with deposit. If the
medium is known for such tendencies, the user has to set
appropriate cleaning intervals. After placing the device out of
service correctly, the diaphragm can usually be cleaned
carefully with a non-aggressive cleaning solution and a soft
brush or sponge. If the diaphragm is calcified, it is recom-
mended to send the device to BD SENSORS for decalcifica-
tion. Please read therefore the chapter "Repair" below.
!
An incorrect cleaning can cause irreparable damages
on diaphragm. Never use spiky objects or pressured air
for cleaning the diaphragm.
n/o (normally opened)
hysteresis mode
9. Return
80 % FSO
75 % FSO
9.1 Recalibration
off
During the life-time of a transmitter, the value of offset and
span may shift. As a consequence, a deviating signal value
in reference to the nominal pressure range starting point or
end point may be transmitted. If one of these two phenom-
ena occurs after prolonged use, a recalibration is recom-
mended to ensure furthermore high accuracy.
9.2 Return
Upon every return of the device, no matter if for recalibration,
decalcification, modifications or repair, it is necessary
to contact us to guarantee a quick execution of your
request. Please inform us by sending an email to:
[email protected]. Include the number of devices sent
and request a RMA. Afterwards clean the device, pack it
shatterproof and send it to BD SENSORS indicating the
RMA.
10. Disposal
The device must be disposed according to the
European
2003/108/EG (on waste electrical and electronic
equipment) Waste of electrical and electronic
equipment may not be disposed by domestic
refuse!
WARNING! Depending on the measuring medium,
®
deposit on the device may cause danger for the user
PC's
and the environment. Comply with adequate precau-
tions for purification and dispose of it properly.
11. Warranty conditions
The warranty conditions are subject to the legal warranty
period of 24 months from the date of delivery. In case of
improper use, modifications of or damages to the device, we
do not accept warranty claims. Damaged diaphragms will
also not be accepted. Furthermore, defects due to normal
wear are not subject to warranty services.
12. Error handling
no output signal although
LEDs are working
no output signal and
LEDs are not working
device does not respond to
pressure change
little shift of the output
signal
large shift of the output
signal
If you detect an error, please try to eliminate it by using this table or send the device to our service address for repair.
!
Improper action and opening can damage the device. Therefore repairs on the device may only be executed by the manu-
facturer!
13. Declaration of conformity / CE
The
delivered
The applied directives, harmonised standards and docu-
ments are listed in the EC declaration of conformity, which is
available
download/certificates.
Additionally, the operational safety is confirmed by the CE
sign on the manufacturing label.
Directives
2002/96/EG
and
Malfunction
Possible cause
line break
wrong setting of the set
points
defective sensor
diaphragm is contami-
nated
diaphragm is damaged
device
fulfils
all
legal
online
at:
http://www.bdsensors.com/products/
Error detection / corrective
inspect all connecting lines of the contacts (including the connecting
plugs)
verify that all switch parameters are useful and permitted
(e.g. the set parameters must lie within the applied pressure range)
please send the device for inspection to our service address
if a contamination is suspected, please send the device to
BD SENSORS for repair
if a damage (e. g. by overpressure) is suspected, please send the
device to BD SENSORS for repair
requirements.
DS6_E_190509