Adjustment and startup
Ensure the input voltage range is correct.
Set desired under and over voltage value by turning, respectively, the upper and middle dials.
Undervoltage adjustment dial
Typology
Linear selection from 2 to 22%
Resolution
2% setpoint increase per notch
Function
Relative undervoltage setpoint
Overvoltage adjustment dial
Typology
Linear selection from 2 to 22%
Resolution
2% setpoint increase per notch
Function
Relative undervoltage setpoint
Set the desired delay on alarm, if required, by turning the lower dial.
Typology
Logarithmic adjustment from 0.1 to 30 s
Resolution
From 100 ms/notch at 0.1 s to 10 s/notch at 30 s
Function
Alarm ON delay setting for undervoltage and overvoltage
Turn power ON, if all the 3 phases are present, in the proper sequence, and the value within the set limits, the
green LED turns ON, the output relay and the yellow LED are ON.
4