SYSTEM SET-UP & CHECKOUT
Skip set up and proceed to INSTALLER TEST MODE on page 9 unless:
• A Model A77 or other external control is to be installed
• changing the air sampling rate
1. Check all wiring�
2. Make sure the wire access cover has been snapped back onto the
on-board control�
3. Plug unit in and turn power switch to ON�
4. The on-board control screen should display OFF�
90-1854
NOTE: If the display backlight is not on, the first button press (any
button) will only turn on the backlight� Press the button a second time
to achieve function�
5. Hold the MODE button on the on-board control for 3 seconds to
enter the Installer Set-up Menu�
6. Navigate through the following screens to set up the dehumidifier
for the installed application�
Use the UP or DOWN arrows to select items and use MODE to
switch to the next set-up option� To exit installer set-up, all options
must be scrolled through using the MODE button�
7. After the installer set up options have been completed, DONE will
blink for 3 seconds and the control will return to the OFF screen�
90-1854
AIR SAMPLING
90-1854
frequently to minimize humidity swings, but increases cost to operate
due to more frequent fan operation� Press MODE when done to move to
the next screen�
RH OFFSET
90-1854
Use the UP or DOWN button to
adjust how frequently the
dehumidifier samples the air to
determine whether or not to
dehumidify� Fewer minutes means
the dehumidifier will sample more
An offset can be applied to the
on-board humidity reading to avoid
discrepancies with other humidity
measuring devices in the home� Use
the UP/DOWN arrows to select an
offset from -5% to 5%� Press MODE
to exit the installer set-up screens�
INSTALLER TEST MODE
If everything is properly wired, the dehumidifier and all of the
wired components will turn on and off during Installer Test
Mode to demonstrate that all are properly operating� Installer
Test Mode lasts for four (4) minutes� If the ON/OFF button is
pressed during test mode, the dehumidifier will exit Installer
Test Mode and return to the OFF screen�
DEHUMIDIFICATION ONLY
90-1854
If the dehumidifier is not
already OFF, press the ON/
OFF button to turn it off�
90-1854
Press and hold the ON/
OFF button and MODE
buttons for 3 seconds� The
measured humidity, AIR
SAMPLING and TEST will
show on the display�
90-1854
After three (3) minutes the
dehumidifier compressor
will turn on and
DEHUMIDIFYING will
replace AIR SAMPLING on
the control screen�
90-1854
After one minute of
compressor operation, all
outputs will turn off and
DONE will blink for 3
seconds and then return to
the OFF screen�
90-1854
90-1854
English 9