AIRTAK C-25 through C-8000 Petunjuk Pemasangan, Pengoperasian, dan Pemeliharaan - Halaman 3
Jelajahi secara online atau unduh pdf Petunjuk Pemasangan, Pengoperasian, dan Pemeliharaan untuk Pendingin AIRTAK C-25 through C-8000. AIRTAK C-25 through C-8000 12 halaman. Refrigerated water chillers
AIR/TAK Refrigerated Fluid Chillers are of the high-efficiency type, designed to effectively remove heat
from process cooling fluids by means of a refrigeration process. The process fluid temperature is
reduced to the temperature required by your machinery.
AIR/TAK chillers are completely automatic in all respects. As with all AIR/TAK products, minimal
maintenance is required. It is our recommendation that this manual be followed for any maintenance that
might be required. Any, and all, service should be performed by a qualified refrigeration technician, who
is trained in the service of refrigerated water chillers.
Upon receiving your chiller:
1. Inspect the shipping carton for any apparent damage.
2. After removing the crate, inspect the unit for any hidden damage.
3. Report any damage immediately to the carrier and notify your supplier.
Selecting the proper location:
Air-cooled chillers must have cool room air made available to prevent a heat build-up in the area where
the chiller is installed. An exhaust system is recommended to avoid recirculation of hot air from the
condenser.
Room temperature at the selected location should not exceed 100°F (35°C), 60 HZ: or 77°F (25°C), 50
HZ, and should not be lower than 50°F (10°C). High room temperatures can effect the efficiency of the
chiller. Every 10°F increase in ambient temperature above 95°F (35°C) will result in a 6% decrease in air
cooled chiller performance, resulting in higher outlet temperatures and increased operating costs.
To assure an unrestricted flow of cool air through the refrigeration condenser, a minimum distance from
the cabinet to the nearest wall of twenty-four inches must be maintained.
All outside installations must have weather protection. Minimum protection should include a shed roof.
Air-cooled units must be protected against the wind.
Outside ambient temperature must not exceed 100°F (38°C) nor be lower than 50°F (10°C) where a
standard unit is to be located. If ambients below 50°F (10°C) are anticipated, the chiller should be
equipped with an optional ultra-low ambient package.
A. INTRODUCTION
B. RECEIVING
C. LOCATION
3