Anderson Thermal Solutions – VFC86 Burner Operation Manual
combustion chamber is purged. If it is ignited at a low temperature, it needs to be replaced
with 5 times the volume of the combustion chamber to avoid explosion.
However, it is not necessary to purge when the temperature is higher than 750°C. Air pipe
or gas pipe connected with burner should be tight enough with no leakage, also the
periodically check air or fuel nozzles of the burners to prevent to be blocked by dust, slag
or other materials.
ATTENTION:DANGER OF BEEN BURNT
When burner in operation, combustion is severe, so the burner must be fixed. Hoses or
cables in area of the combustion system must be suitable for high temperature, to prevent
high temperature failure or cause safety accidents. Burners should be periodically
inspected and cleaned. Copper wire brush may be used, if necessary, to clean burner head.
The burner system should be checked twice a year for safety operation.
Burner commissioning shall take care of ignition position, minimum and maximum output
position. Following interlocks will cause emergency stop, including gas low pressure, high
pressure or low combustion air pressure, as well as emergency stop is trigged, the main
power is out, UV signal failure or kiln safety conditions (such as high temperature limit, flue
system opening, etc.) will cause the burner lockout. Users need to know the maintenance
interval recommended by the manufacturer and the interval specified by national laws,
whichever is shorter.

4. Fuel Information

The following table shows combustion fuel characters of natural gas and oxygen, safety
rules must be obeyed when operation carried out.
Fuel
Natural gas
Low Calorific value
35,900 [kJ/m
3
]
Composition
>98% CH
4
Reference conditions
1,013.25 mbar, 0°C

5. VFC86 Series Burner Description

VFC86 burners are the patented products of Anderson Thermal Solutions (Suzhou) Co., Ltd.
It is modular designed used for flue gas re-combustion. It is in-duct burner which can be
located directly in the exhaust air. The burner is also suitable for fresh air operation.
VFC86 burner is made up of a frame, flame retaining plate, gas nozzle and gas supply
manifold, the sheet metal size 150mmX150mm is fixed in the gas manifold. 8 Slots where
cut from the sheet metal, with 2 nozzles symmetrically located in the plate.