Atlantic Boilers RELAX DIGITAL 18 Panduan Pengoperasian & Pemeliharaan - Halaman 11

Jelajahi secara online atau unduh pdf Panduan Pengoperasian & Pemeliharaan untuk Ketel uap Atlantic Boilers RELAX DIGITAL 18. Atlantic Boilers RELAX DIGITAL 18 13 halaman. Electric boiler

6).

DELIVERY and OFFLOADING

Keep the RELAX DIGITAL in its original packing until it arrives on site
The ambient temperature must be maintained between 10degC & 50degC
The relative humidity must be maintained between 30% & 80%
Arriving on site, the RELAX DIGITAL must be handled safely
Make use, if possible, of the factory pallet & a fork truck
Make use, if possible, of the RELAX DIGITAL lifting eyes
7).

MAINTENANCE

The maintenance intervals can be predicted for each installation
AT COMMISSIONING
 Check the cold feed & expansion system operates correctly
 Check all immersion heater couplings are sound
 Manipulate & check the safety & temperature/pressure relief valves
 If the high temperature limit locks out, correct any fault & reset by hand
ANNUALY
 Check all immersion heater couplings are sound
 Flush out the immersion heater cells
 Check all automatic air vents, safety & relief valves, thermostat switches
 Check the shunt pump circulation
DO NOT
 Stop the pump whilst the boiler is operating
 Release water from the system whilst the boiler is operating
11