Jelajahi secara online atau unduh pdf Manual untuk Pengontrol Beckett GeniSys 120V. Beckett GeniSys 120V 13 halaman. Advanced burner control

Features
◦
Thermostat / Operating (if applicable) and Limit Control Compatible
◦
Welded Relay Protection
◦
Limited Recycle
◦
Limited Reset
◦
3 Status Lights
◦
Valve-On Delay / Motor-Off Delay (Field programmable with Beckett add-on Display)
◦
15 Second Lockout Time
◦
Interrupted or Intermittent Duty Ignition
◦
Technician Pump Priming Mode
◦
Disable Function
◦
Communication Ports (2)
Table 1 - Models and Cross Reference Guide
Beckett GeniSys
Control Part No.
7505A 0000
7505B 1500
7505P 1515
7505P 1530
7505P 152M
1 - Beckett snap-on alarm module required for direct replacement of this control.
2 - Valve-on delay and motor-off delay timings on all models are programmable with Beckett snap-on
programming display. Other factory set timings are available. Contact Beckett for alternate timings.
2
Lockout
Valve-on
Time
delay time
15 sec
-
15 sec
15 sec
15 sec
15 sec
15 sec
15 sec
15 sec
15 sec
Motor-off
2
delay time
2
-
R7184A, R8184G
-
15 sec
R7184P, R7184U
30 sec
R7184P, R7184U
2 min
R7184P, R7184U
Replaces
Honeywell:
48245, 40200,
42230, 50200
R7184B
1
1
1
Replaces
Carlin:
1
-
60200
1
60200
1
60200
1